CVM1-PA208 Omron, CVM1-PA208 Datasheet - Page 78

no-image

CVM1-PA208

Manufacturer Part Number
CVM1-PA208
Description
CV/CVM1 POWER SUPPLY, AC
Manufacturer
Omron
Datasheet

Specifications of CVM1-PA208

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Terminals Screws and Crimp Terminals
3-6-6 Grounding
62
Power Supply Unit Wiring
!
WARNING
Note The power supply terminal block is detachable so be sure to check the terminal
Connect the lead wires to the terminals as shown below. Tighten the screws to a
torque of 0.8 Nm.
Attach solderless type (crimp) terminals to the ends of the lead wires, using ter-
minals having the dimensions shown in the following diagram suitable for M3.5
self-raising screws.
block to be sure it is firmly locked in place after wiring the terminals.
Always attach crimp terminals to the power supply lines to ensure proper
connection. Connecting loose wires can cause fires.
The line ground (LG:
neutral terminal. Short the line ground terminal to the ground (GR:
improve noise resistance.
To avoid electrical shock, attach a grounded AWG 14 wire (cross-sectional area
of 2 mm
and must be checked periodically to be sure that environmental conditions have
not deteriorated ground capacity. Do not use a wire longer than 20 m.
PC operation may be adversely affected if the ground wire is shared with other
equipment or if the ground wire is attached to the metal structure of a building.
20 mm max.
2
) to the ground terminal. The ground resistance must be 100 W or less
0.8 N•m torque
7 mm max.
) terminal of the Power Supply Unit is a noise-filtered
M3.5 self-raising screws.
Section
) terminal to
3-6