66
Power Supply Unit Wiring
!
WARNING
START INPUT wiring (short-circuit) is required for the Power Supply Units on the
CPU Rack. When CVM1D operation is started by an external sequence, the
contacts must be connected so that the START INPUT terminals turn ON for
both Power Supply Units at the same time. If they do not turn ON simultaneously
for both Power Supply Units, an error will be generated.
The START INPUT terminals are short-circuited at the factory with a short bar.
The short bar can be removed and the terminals wired to a 10-mA, 24-VDC ex-
ternal input to control PC operation. When these terminals are open, PC opera-
tion will stop.
Connect the lead wires to the terminals as shown below. Tighten the screws to a
torque of 0.8 N•m max.
Attach solderless type (crimp) terminals to the ends of the lead wires, using ter-
minals having the dimensions shown in the following diagram suitable for M3.5
self-raising screws.
The RUN output terminals will be ON (closed) when the PC is operating in RUN
or MONITOR mode. These terminals can thus be wired to provide an external
signal indicating the operating status of the PC, such as is used in the emergen-
cy stop circuit shown in 3-6-1 Emergency Stop Circuit.
Maximum switching capacity:
250 VAC/2 A (COS φ = 1)
250 VAC/0.5 A (COS φ = 0.4)
24 VDC/2A
Always attach crimp terminals to the wires to ensure proper connection.
Connecting loose wires can cause fires.
20 mm max.
0.8 N•m torque
7 mm max.
M3.5 self-raising screws.
START input
Section
3-6