FPS100024 TDK Corporation, FPS100024 Datasheet - Page 30

PWR SUP FNT END 24V 960W 40A

FPS100024

Manufacturer Part Number
FPS100024
Description
PWR SUP FNT END 24V 960W 40A
Manufacturer
TDK Corporation
Series
FPSr
Type
Commercialr
Datasheets

Specifications of FPS100024

Power Supply Type
Switching (Closed Frame)
Voltage - Output
24V
Number Of Outputs
1
Power (watts)
1000W
Applications
Commercial
Voltage - Input
85 ~ 265VAC
Mounting Type
Chassis Mount
1st Output
24 VDC @ 40A
Size / Dimension
1.61" L x 5" W x 11.4" H (40.9mm x 127mm x 289.6mm)
Power (watts) - Rated
960W
Operating Temperature
0°C ~ 70°C
Efficiency
86%
Approvals
CE, EN, UL
Line Regulation
0.4%
Load Regulation
0.8%
Power Supply Output Type
Fixed
No. Of Outputs
1
Output Voltage
24V
Output Current
40A
Power Rating
960W
Input Voltage
85V AC - 265V AC / 120V DC To 360V DC.
Brand/series
FPS1000 Series
Configuration
Enclosed
Operation
Linear
Output
24 VDC @ 40 A
Power, Output
960 W
Primary Type
AC-DC
Special Features
High Efficiency, Hot Swappable, PFC, Remote On/Off, Remote Sense
Voltage, Input
85 to 265/120 to 360 VAC/VDC
Voltage, Output
24 VDC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
RoHS Compliant part
Other names
285-1237

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
FPS100024
Manufacturer:
TDK-LAMBDA
Quantity:
232
Part Number:
FPS100024/P
Manufacturer:
TDK-LAMBDA
Quantity:
232
Part Number:
FPS100024/PS
Manufacturer:
TDK-LAMBDA
Quantity:
232
Part Number:
FPS100024/S
Manufacturer:
TDK-LAMBDA
Quantity:
232
10.7.3 Making the load connections
wires for load connection at the FPS-S1U.
10.7.4 Rear panel description
Fig. 10-1: FPS-S1U Rear panel
1. Mounting brackets. Use M6x12 screws to fix the FPS-S1U to the rack.
2: DB25 connector for control and monitoring signals.
3: Output voltage terminals. Use M6x16 screws and M6 lug to connect the load wire. The recommended
4. DIP switch for I
5. IEC320 AC inlets, shown for FPS-S1U rack. For FPS-S1U/P, there are no IEC320 inlets on the rack.
Pin No Function
10.7.5 Control and monitoring signals connector
The load wires should be properly terminated with terminals securely attached. DO NOT use unterminated
1
2
3
4
5
6
7
8
tightening torque is 42~56Kgf.cm.
1
V_TRIM_B
TEMP_ALARM_B
DC_OK_B
TEMP_ALARM_A
ON/OFF_A
DC_OK_A
V_TRIM_A
+12V_AUX
2
2
C option address setting. Refer to Chapter 14 for details.
Hazardous voltages may exist at the outputs and the load connections
when using a power supply with a rated output greater than 40V. To
protect personnel against accidental contact with hazardous voltages,
ensure that the load and it's connections has no accessible live parts.
Ensure that the load wiring insulation rating is greater than or equal to
the maximum output voltage of the power supply.
Description
Connection for output voltage trimming of FPS1000 unit "B". The voltage can be
trimmed within its range specifications.
Open collector signal, referenced to pin 11 (Signal Return). On when the internal temperature
of FPS1000 unit "B" is within safe limit, Off approx. 10°C below Thermal shut down. The
maximum sink current is 10mA and the maximum external voltage is 15V.
Open collector signal, referenced to pin 11 (Signal Return). On when the output voltage
of FPS1000 unit "B" is higher than ≥ 80%+/-5%. The maximum sink current: 10mA
and the maximum external voltage is 15V.
Open collector signal, referenced to pin 11 (Signal Return). On when the internal temperature
of FPS1000 unit "A" is within safe limit, Off approx. 10°C below Thermal shut down. The
maximum sink current is 10mA and the maximum external voltage is 15V.
Turns the output of FPS1000 unit "A" to On and Off by electrical signal or dry contact
between pin 5 and pin 11 (Signal Return). 0~0.6V or Short: On, 2~15V or Open:
Off. The maximum source current is 2.6mA.
voltage of FPS1000 unit "A" is higher than V
current: 10mA and the maximum external voltage is 15V.
Connection for output voltage trimming of FPS1000 unit "A". The voltage can be
trimmed within its range specifications.
Auxiliary voltage output, 11.2~12.5V, referenced to pin 11 (Signal Return). The
maximum load current is 0.25A. This output has built in Oring diode and is not controlled
by the On/Off control.
Open collector signal, referenced to pin 11 (Signal Return). On when the output
3
!
27
WARNING
4
out
≥ 80%+/-5%. The maximum sink
FPS-S1U Instruction Manual
5
1