3-1 Routing Table Overview
3-1-5 Operating Procedures Prior to Routing Table Transfer
3-1-5
3-6
Network Configuration Procedures
Note
Operating Procedures Prior to Routing Table Transfer
Creating the FINS Local Routing Tables Online
When configuring the network, connect the CX-Integrator directly to each node (CPU
Unit) that will participate in the network and set the routing tables (FINS local routing
tables).
This section describes the operating procedures necessary to create the routing tables
for the first time up to the point where the files are transferred to the PLCs.
Connect online with the PLC directly connected to the CX-Integrator.
Select Network – Auto Online or Network – Work Online from the CX-Integrator's menu bar.
Start the Routing Table Component. (Start the PLC routing table.)
Right-click the Communications Unit or Port in the Online Connection Information Window select Start Routing Table from the
popup menu, or select Tools - Start Routing Table from the CX-Integrator's menu bar.
Check the routing tables for errors.
Select Options – Check Routing Table for errors from the PLC routing table menu.
Transfer the routing tables to the PLC (from the computer to the directly connected PLC).
Select Options – Transfer to PLC from the PLC routing table menu.
Save the created routing tables.
Select File – Save Local Routing Table File from the PLC routing table menu.
Create the FINS local routing tables (in the PLC routing tables).
Set the gateway counter. (CS/CJ-series CPU Units must be unit version 3.0 or later.)
Click the SIOU Tab when the PLC routing tables are displayed, right-click the local PLC's icon, and select Set Gateway Counter
from the menu.
Create the local network table.
Create the relay network table.