CS1W-CN625 Omron, CS1W-CN625 Datasheet - Page 130
![no-image](/images/manufacturer_photos/0/4/494/omron_sml.jpg)
CS1W-CN625
Manufacturer Part Number
CS1W-CN625
Description
CBL,PROG
Manufacturer
Omron
Datasheet
1.CS1W-CN625.pdf
(336 pages)
Specifications of CS1W-CN625
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
- Current page: 130 of 336
- Download datasheet (10Mb)
3-2-5
Note
Note
Note
Transferring Routing Tables
When transferring the FINS local routing tables, the tables can be transferred only to
the directly connected PLC (with node address 0). The tables cannot be transferred to
any other PLC in the network (i.e., to a node address other than node 0).
If routing tables are transferred to the PLC from a Programming Device, the CPU Bus
Unit will be reset. The Unit is reset in order to read and enable the routing tables that
were transferred. Before executing the routing table transfer, verify that no equipment
will be damaged and it is safe for the CPU Bus Unit to be reset.
The routing tables cannot be transferred to another network layer. When transferring
to a different network layer, directly connect the CX-Integrator to a PLC in that network
and transfer the routing tables.
Use the following procedure to transfer the routing tables that were created online or
offline to PLC1. The computer must be directly connected to PLC1 and online.
1. Verify that PLC1 is connected directly to the CX-Integrator and online, display the
2. The following dialog box will be displayed to confirm the transfer. To proceed with
3. The routing tables (local network table and relay network table) will be transferred
PLC Routing Table Window, and select Options – Transfer to PLC.
from the computer (CX-Integrator) to PLC1.
The following dialog box will be displayed after the transfer is completed.
This step completes the transfer of the routing tables to PLC1. Use the procedure
outlined above to transfer the routing tables to PLC2 and PLC3.
Note: The following message will be displayed if a CS/CJ-series Unit with no version
Click the Yes Button to change the gateway counter setting to Standard and transfer the
routing tables.
Click the No Button to cancel the routing table transfer.
the transfer to the PLC, click the Yes Button.
number is being used and the gateway counter was set to Expand in the Gateway
Counter Setting Dialog Box.
3-2 Setting the Routing Tables
3-2-5 Transferring Routing Tables
3-21
Related parts for CS1W-CN625
Image
Part Number
Description
Manufacturer
Datasheet
Request
R
![CS1W-DA041](/images/manufacturer_photos/0/4/494/omron_tmb.jpg)
Part Number:
Description:
MODULE,ANALOG OUT,4CH
Manufacturer:
Omron
Datasheet:
![CS1W-AD081-V1](/images/manufacturer_photos/0/4/494/omron_tmb.jpg)
Part Number:
Description:
MODULE, ANALOG IN, 8CH
Manufacturer:
Omron
Datasheet:
![CS1W-CN118](/photos/21/48/214810/4682295_tmb.jpg)
Part Number:
Description:
Connector Cable
Manufacturer:
Omron
Datasheet:
![CS1W-CN226](/photos/21/48/214810/4682295_tmb.jpg)
Part Number:
Description:
Cable Connector
Manufacturer:
Omron
Datasheet:
![CS1W-BAT01](/images/manufacturer_photos/0/4/494/omron_tmb.jpg)
Part Number:
Description:
"BATTERY,CPU,CS1 SERIES ONLY"
Manufacturer:
Omron
Datasheet:
![CS1W-CN114](/images/manufacturer_photos/0/4/494/omron_tmb.jpg)
Part Number:
Description:
"CABLE,CS1/ CQM1-PRO01,0.1m"
Manufacturer:
Omron
Datasheet:
![CS1W-BC033](/images/manufacturer_photos/0/4/494/omron_tmb.jpg)
Part Number:
Description:
BACKPLANE,CS1 CPU,3 SLOTS
Manufacturer:
Omron
Datasheet:
![CS1W-BC083](/images/manufacturer_photos/0/4/494/omron_tmb.jpg)
Part Number:
Description:
"BACKPLANE,CS1 CPU,8 SLOTS"
Manufacturer:
Omron
Datasheet:
![G6S-2G](/images/no-image3.png)
Part Number:
Description:
G6S-2GLow Signal Relay
Manufacturer:
Omron Corporation
Datasheet:
![G3NE-220T](/images/no-image3.png)
Part Number:
Description:
Compact, Low-cost, SSR Switching 5 to 20 A
Manufacturer:
Omron Corporation
Datasheet:
![G6K-2G-Y](/images/no-image3.png)
Part Number:
Description:
Manufacturer:
Omron Corporation
Datasheet: