8-2
8-2-1
8-2-2
Transferring Screen Data through the PLC
Procedure
Overview
The NS-Designer can be started from an NS-series PT in the Network Configuration
Window and created screen data can be transferred through a CS/CJ-series PLC (see
note) to a serially connected NT-series PT.
Note: In order to transfer screen data through the PLC, the PLC must be a CS/CJ-series PLC
The following example demonstrates how to transfer screen data through the CPU
Unit’s serial port.
1. Select Network – Work Online or Network – Auto Online from the menu bar.
2. The Select Serial Port Dialog Box will be displayed.
• Serial connection
• Network connection
Note: Since the RS-232C port is used by the PT, the peripheral port
(Toolbus or Host
Link, see note)
Computer
(Start NS-Designer from New CX-Net.)
In this case, Auto Online has been selected.
Select the desired computer communications port from the pull-down menu and
click the OK Button.
must be used to make a direct serial connection to the computer.
with a CPU lot number of 030201 (manufactured February 1, 2003) or later. In addition,
the CPU Unit must be a CS1G-H, CS1H-H, CS1D-S, CJ1M, CJ1G-H, or CJ1H-H. (The
screen data cannot be transferred through a CS1D-H).