4-1-2
Step 1: Selecting the Data Link Setting Method
Step 2: Data Link Allocation Area Settings
Step 3: Starting the Data Links
Overview of Procedure by Data Link Setting Method
Either of the following methods can be used.
1) Select either user-set data links or automatically set data links after selecting
2) Directly set the software switches in the allocated DM Area words.
Note: The settings in the DM Area can also be made from the Special I/O Unit settings in the I/O
Manual:
Automatic:
Automatic or
manual:
Online - Automatic Data Link Setup from the Data Link Component.
1. Right-click the Controller Link Unit or SYSMAC LINK Unit in the I/O Table Window, select
2. Place the CX-Programmer online and transfer the parameters to the PLCs. (The Compare
Unit Setup from the popup menu, and then select Data Link mode from the Edit
Parameters Dialog Box.
Controller Link Unit: Select Manual setting, Automatic setting (equality layout), or
Automatic setting (1:N allocation)
SYSMAC LINK Unit: Manual setting, Automatic setting (CIO Area only), Automatic setting
(DM Area only), or Automatic setting (CIO + DM Areas).
Button can be clicked to set the parameters which verifying against the setting data in the
actual PLCs.
Table Window for CX-Programmer Ver.6.0 or higher.
Select Table - Wizard from the Data Link Component online or select
File - New, create the data link tables, and then go online and
transfer the tables to all nodes in the network.
Use one of the following methods.
1) Select Online - Automatic Data Link Setup from the Data Link
2) Directly set the parameter area for automatically allocating data
Note: The Special I/O Unit settings in the I/O Table Window can also be used
Use one of the following methods.
1) Select Online - Data Link Operation/Status from the Data Link
2) Turn ON the Data Link Start Bit in the DM Area words allocated
Note: The Special I/O Unit settings in the I/O Table Window can also be used
4-1-2
Component and set the parameters for automatically setting data
links.
links in the allocated DM Area words.
Component, select the RUN Option under Operation and then
click the Set Button.
to the start node and then cycle the power to the PLC.
(Alternately, leave the power to the PLC ON and turn the Data
Link Start Bit OFF and then back ON.)
to set parameters for automatically allocating data links and then these
parameters can be transferred to the startup node.
to set parameters for automatically allocating data links, the Data Link
Start Bit can be set to be turned ON and then these parameters can be
transferred to the startup node.
Overview of Procedure by Data Link Setting Method
4-1
Overview