CS1W-CN625 Omron, CS1W-CN625 Datasheet - Page 285

no-image

CS1W-CN625

Manufacturer Part Number
CS1W-CN625
Description
CBL,PROG
Manufacturer
Omron
Datasheet

Specifications of CS1W-CN625

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
6-12 Downloading the Network Configuration/Device Parameters to Devices
6-12-3 Resetting the Device
6-12-3
6-56
Note
Component - Reset
Resetting the Device
When the devices are reset, communications errors will temporarily occur. For this
reason, do not reset the devices while the master-side PLC (CPU Unit) is operating.
To enable the new settings, use the following procedure to reset the network device.
1. Place the CX-Integrator online.
2. Select the device in the Network Configuration Window.
3. Select Device - Reset.
4. Click the Yes Button.
The following confirmation dialog box will be displayed.
The progress window will be displayed and the devices will be reset.
The new settings will be valid after the devices have been reset.