3-1 Routing Table Overview
3-1-2 Network Conditions That Require Routing Tables
3-1-2
3-4
Network Conditions That Require Routing Tables
Routing Table Settings not Required
Setting Example
The following example shows the routing tables that route communications from PLC1
(network address 1, node address 1) to PLC4 (network address 3, node address 2).
When necessary, set the routing tables (local network table and relay network table)
in the PLC as shown in the following table.
PLC1 Local Network Table
Unit number
PLC1 Relay Network Table
1) Setting details
2) Setting details
Destination
address (a)
Local node PLC1
Node address 1
(Unit number 0)
To go to network address 3, first it is
necessary to go to node address 3 (c)
in network address 1.
Destination network (a) sets both
network address 3, and network
address 2, which must be passed in
order to reach network address 3.
network
(b)
(b)
Network usage
One Communications Unit is mounted
in the PLC, and that Unit is connected
to one network.
Two or more Communications Units are
mounted to one PLC (CPU Unit).
Routing tables have been set in at least
one other node in the same network.
Communications are made across
network levels.
Routing tables are not required when just one Communications Unit is installed in
each PLC and those Communications Units are connected in a single network.
2
3
(c)
0
(c)
Network address 1
network
address
Relay
Local network
address
(b)
1
1
(a)
1
address
Relay
node
(c)
3
3
Relay node PLC2
Node address 3 (Unit number 0)
(a)
..1)
..2)
Node address 1
(Unit number 1)
3) Setting details
PLC2 Local Network Table
Unit number
PLC2 Relay Network Table
address (a)
Destination
network
To go to network address 3, it is
necessary to go to node address 2
(c) in network address 2.
3
0
1
address
network
(c)
Local network
address
Relay
(b)
2
Network address 2
(b)
1
2
address
Relay
node
(c)
2
Node address 2
(Unit number 0)
Relay node PLC3
(a)
..3)
Local network table
The local network table shows that it is
necessary to pass through unit number
1 in the local CPU Rack To go to
network address 3.
4) Setting details
PLC3 Local Network Table
Unit number Local network
PLC3 Relay Network Table
Destination
address (a)
network
Not required
(a)
The destination network
address is set to network
address 1(a).
0
1
1
Required
Required
Required
(c)
Node
address 1
(Unit
number 1)
address
address
Network address 3 (destination network)
network
Relay
(b)
2
(b)
2
3
Routing table
address
Relay
node
Target node PLC4
(c)
1
..4)
PLC4 Local Network Table
Unit number
PLC4 Relay Network Table
5) Setting details
6) Setting details
Destination
address (a)
network
Destination network (a) sets
both network address 1 that has
a destination node of PLC4, and
network address 2, which must
be passed in order to reach
network address 1.
(a)
1
2
Relay network table
0
Not required
Not required
Not required
Node address 2
(Unit number 0)
Required
address
network
Local network
address
Relay
(a)
(b)
3
3
(c)
(c)
3
address
Relay
node
(c)
1
1
(b)
(b)
..5)