6-8 Manual I/O Allocations
6-8-2 Changing the First Address of Output/Input Block
6-8-2
6-30
Allocation Status of Blocks 1 and 2
Component - Parameter - Edit - I/O Allocation Tab - Setup Button
Changing the First Address of Output/Input Block
The block allocation status list displays the words of the CPU Unit and the product
names of devices allocated in the respective areas of the CPU Unit.
The start bit and the word address for each device are indicated in the Ch column.
Example:
No words in the CPU Unit will be displayed for any memory block that is not in use.
To change the output/input block allocation areas in the I/O memory of the CPU Unit,
use the following procedure.
1. Click the Setup Button of the block to be changed.
2. The following dialog box will be displayed.
3300:Bit00: Starts with bit 00 (LSB) of word CIO 3300.
3300:Bit08: Starts with bit 08 (MSB) of word CIO 3300.
Word address (Example 3300)
First bit address (Bit00)
Product name of slave
Allocated the bytes beginning
with bit 08 of word CIO 3300.
Therefore, the product name for
3300:Bit08 is left blank.
Example: Allocation starts with bit 00 (LSB)
of word CIO 3300.