CS1W-CRM21 Omron, CS1W-CRM21 Datasheet - Page 184

no-image

CS1W-CRM21

Manufacturer Part Number
CS1W-CRM21
Description
CS1 CompoNet Master
Manufacturer
Omron
Datasheet

Specifications of CS1W-CRM21

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
3-2 Setting the Routing Tables
3-2-10 Transferring Routing Tables to a Network PLC through a Direct Serial Connection
3-2-10
3-28
Note
Transferring Routing Tables to a Network PLC through a
Direct Serial Connection
Computer (CX-Integrator)
Transfer Procedure
The data transfer procedure described in this section is applicable to the FINS local
routing tables only.
Use the following procedure to transfer the FINS local routing tables to a PLC in the
network (see note 2) through the PLC that is connected by a direct serial connection
with network address 0 and node address 0.
The following example shows how to transfer the routing tables to PLC2, PLC3, PLC4,
and PLC5, which are in the same network as directly connected PLC1, as shown in
the network configuration diagram.
1. Confirm that PLC1 is connected directly to the CX-Integrator by a serial
2. Select Tools – Start Routing Table.
Direct serial connection
Note 1: The following conditions are required to use this function.
Note 2: The FINS local routing tables can be transferred only to a PLC in the same network
Connect online with
network address = 0,
and node address = 0.
connection (with network address = 0, and node address = 0), and online.)
It is also possible to right-click the Communications Unit or Port in the Online
Connection Information Window select Start Routing Table from the popup
menu.
Network address 0
as the PLC connected directly by a direct serial connection. The transfer cannot
cross a network level to another network.
Network address 0
Ethernet Unit with
unit number 0
Initial connection to PLC1
Controller Link Unit with
unit number 1
The local network table is
not set in this PLC.
PLC4
Node address 2
Use CX-Integrator Version 2.1 or higher.
The PLC must have a CS/CJ-series CPU Unit with unit
version 4.0 or later.
PLC2
Node address 2
Ethernet
PLC5
Node address 3
Controller Link
PLC3
Node address 3

Related parts for CS1W-CRM21