CS1W-CRM21 Omron, CS1W-CRM21 Datasheet - Page 259

no-image

CS1W-CRM21

Manufacturer Part Number
CS1W-CRM21
Description
CS1 CompoNet Master
Manufacturer
Omron
Datasheet

Specifications of CS1W-CRM21

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Obtaining I/O Size Information from the Master Scan List
Parameter Auto Update When I/O Size Changed
Note
If the function to automatically update the I/O size is enabled and there is no EDS file,
some operations will cause the I/O size in the master scan list to be updated to zero.
For this reason, the function to automatically update the I/O size should normally be
disabled.
When connecting the CX-Integrator to a network that is already operating, for example
using OMRON Master Units with fixed allocation, the slave I/O size can be obtained
from the master scan list for use in setting.
However, this is possible only with OMRON masters. Also, the slave I/O size cannot
be obtained from the slave function of the CS1W-DRM21(-V1) and CJ1W-DRM21.
Use the following procedure to obtain the I/O size from a master scan list.
1. Select the desired slave, then select View - Property.
2. Click the I/O Information Tab.
3. Click the Get I/O Size from the Scanlist Button.
The function to automatically update the I/O size registered on the master scan list
when the I/O size is changed can be switched ON or OFF.
To automatically update the I/O size registered on the master scan list, select Tools -
DeviceNet tool - Parameter Auto Update when I/O Size Changed.
When this function is enabled, the
is set to not automatically update.
mark will be displayed in the menu. The default
6-2-2 Checking and Setting I/O Size
6-2 Setting Slave Parameters
6-7