System Setup
5-7-2
Read Protection
Using Passwords
Password Protection
Password Protection
against Clearing
5-7-3
Automatic Backup to
Flash Memory
Operation Settings at Startup and Maintenance Functions
Program Protection
Flash Memory
1,2,3...
Note
Note
The operating mode at startup for Motion Control Modules will be the same as
that for the Coordinator Module when in Sync Mode, but will be RUN mode
when in ASync Mode.
The FQM1 provides the following kinds of protection for user programs.
Read and display access to the user program area can be blocked from the
CX-Programmer. Protecting the program will prevent unauthorized copying of
the program and loss of intellectual property.
A password is set for program protection from the CX-Programmer and read
access is prevented to the whole program.
1. Register a password either online or offline.
2. Set password protection online.
The program can be protected against unauthorized clearing by inputting the
password “5A5A5A5A” in step 1b of the procedure above. Once this password
has been input, the password protection cannot be cleared by inputting the
password again. The Memory All Clear operation must be executed from the
CX-Programmer in order to clear the password protection.
The user program and parameters are automatically backed up in flash mem-
ory whenever they are written.
Startup
Tab page
(1) If you forget the password, the program in the FQM1 cannot be trans-
(2) If you forget the password, programs can be transferred from the comput-
• The following data is backed up automatically: User program, parameters
a. Select the Module in the Device Type drop-down menu and select
b. Select Protection from the PLC Properties Dialog Box and input the
a. Select PLC/Protection/Set. The Protection Setting Dialog Box will be
b. Click the OK Button.
(including the System Setup, absolute offset data, and analog I/O offset
gain adjustment values), and some DM Area data (only for the Coordina-
tor Module).
ferred to the computer.
er to the FQM1. Programs can be transferred from the computer to the
FQM1 even if the password protection has not been released.
Properties from the View Menu.
password.
displayed.
Startup
Mode
Name
Specifies the
initial operating
mode when the
power is turned
ON.
Details
System Setup disabled
• RUN mode
System Setup enabled
• PROGRAM mode
• MONITOR mode
• RUN mode
Settings
Section 5-7
System Setup
disabled
Default
159