FQM1 programs have special program sections that will control instruction conditions.
The following special program sections are available.
Instruction Combinations
The following table shows which of the special instructions can be used inside other program sections.
Note Instructions that specify program areas cannot be used between two different tasks.
Subroutines
Place all the subroutines together just before the END(001) instruction in all programs but after programming
other than subroutines. A subroutine cannot be placed in a step ladder, block program, or other subroutine. If
instructions other than a subroutine program are placed after a subroutine program (SBN(092) to RET(093)),
those instructions will not be executed.
Programming
Subroutine
IL(002) - ILC(003) section IL(002) and ILC(003)
Step Ladder section
FOR(512) - NEXT(513)
section
JMP0(515) - JME0(516)
section
Block program section
Subroutine
IL(002) - ILC(003)
Step ladder section
FOR(512) - NEXT(513)
JMP0(515) - JME0(516) OK
Block program section OK
Program section
Special Program Sections
Not possible.
OK
Not possible.
OK
SBS(091), JSB(982),
SBN(092), and RET(093)
instructions
instructions
STEP(008) instruction
FOR(512) and NEXT(513)
instructions
JMP0(515) and JME0(516)
instructions
BPRG(096) instructions and
BEND(801) instructions
Subroutine
Instructions
Not possible.
Not possible.
OK
OK
OK
OK
IL(002) -
ILC(003)
section
Subroutine program
being executed.
Section is interlocked
BREAK(514) execu-
tion
Block program being
executed.
Instruction condition
Not possible.
Not possible.
Not possible.
Not possible.
Not possible.
OK
Step ladder
section
Not possible.
OK
Not possible.
OK
Not possible.
Not possible.
FOR(512) -
NEXT(513)
loop
The subroutine program section
between SBN(092) and RET(093)
instructions is being executed.
The output bits are turned OFF and
timers are reset. Other instructions will
not be executed and previous status
will be maintained.
Repeatedly executes instructions in the
loop between FOR(512) and
NEXT(513).
Jumps from JMP0(515) to the next
JME0(516) and treats all instructions in
the jumped section as NOP(000).
The block program listed in mnemonics
between the BPRG(096) and
BEND(801) instructions is being exe-
cuted.
Not possible.
OK
OK
OK
Not possible.
OK
JMP0(515) -
JME0(516)
section
Status
Appendix A
Not possible.
Not possible.
Not possible.
Not possible.
Not possible.
Not possible.
program
section
Block
345