Error Processing
Memory Error Check
Program Error Check
interrupted while backing
Program error occurred
up memory with the CX-
Memory error occurred
Flash Memory Error Flag
No END Error Flag
Task Error Flag
(A405.12) ON?
(A405.11) ON?
(A403.10) ON?
Programmer?
Was power
OFF
OFF
OFF
No
ON
Yes
ON
ON
The internal flash memory's rewrite limit has
been exceeded. Replace the Module.
The power supply was turned OFF during a
memory backup. Transfer the data again.
There was a hardware failure in the internal
memory. Replace the Module.
The called task does not exist. Check the
MSKS instruction that enables the interrupt
task with the corresponding task number.
There isn't an END instruciton in the
program. Add an END instruction.
Turn the power supply OFF and ON again.
Section 9-2