C200H-DA001 Omron, C200H-DA001 Datasheet - Page 43

no-image

C200H-DA001

Manufacturer Part Number
C200H-DA001
Description
2PT-D/A:12-BIT
Manufacturer
Omron
Datasheet

Specifications of C200H-DA001

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
40
SPECIAL I/O MODULES
ANALOG INPUT MODULES
System Configuration
Analog signals, such as voltages and currents, are received
from various sensors through the maximum of 8 inputs
(AD002) and converted into 12-bit binary data.
External input signal range can be freely set to cope with
diverse needs.
Built-in functions included: the scaling function, mean func-
tion, peak hold function, square-root extraction function, and
more.
C200H-AD001
C200H-AD002
Temperature
Pressure
Voltage
Current
Flow
Analog input
C200HX/HG/HE
Analog Input Modules accept a variety of analog signals from
external devices, including both voltage and current ranges.
Both Modules provide 12-bit resolutions and fast access to the
PLC.
Features
Specifications
Cost-effective single-slot modules available with 4 or 8
analog inputs
12-bit resolution
Selectable ranges include 1 to 5 V, 0 to 10 V, and 4 to 20 mA
PART NUMBER
Input points
Voltage input
External
input imped-
in ut im ed
ance
Resolution
Total preci-
sion
Conversion speed
Converted data
Maximum in-
put signals
I/O words required
External connections
Current consumption
Weight
Manual
ut signals
Current
input
Voltage
input
Current
input
Voltage
Current
25 C
77.0 F
0 to
55 C
(32 to
131 F)
Voltage
input
Current
input
C200H-AD001
4
1 to 5V or 0 to 10 V
4 to 20 mA
1 M min.
250
1/4,000 FS
2.5 ms max./pt
12-bit binary
10 (Special I/O area)
Terminal block
550 mA max., 5 VDC
450 g max.
W127
0.5% FS
1.0% FS
15 V max.
30 mA max.
C200H-AD002
8
1 to 5 V, 0 to 10 V, or
--10 to 10 V
Voltage: 0.25% FS
Current: 0.4% FS
Voltage: 0.6% FS
Current: 0.8% FS
12-bit binary or 4-digit
BCD code (selectable)
Connector
450 mA max., 5 VDC
290 g max.
W229

Related parts for C200H-DA001