C200H-DA001 Omron, C200H-DA001 Datasheet - Page 47

no-image

C200H-DA001

Manufacturer Part Number
C200H-DA001
Description
2PT-D/A:12-BIT
Manufacturer
Omron
Datasheet

Specifications of C200H-DA001

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
44
SPECIAL I/O MODULES
TEMPERATURE CONTROL MODULES
Specifications
PART NUMBER
Current transformer detection current
Input points (no. of loops)
Temperature control mode
Preset memory bank items (8 max.)
Setting/Indication accuracy
Proportional band
Integral (reset) time
Derivative (rate) time
Control period
Sampling period
Input shift range
Alarm output mode
No. of banks
Internal current consumption
External supply voltage
Weight
Manual
C200H-TC00
C200H-TC10


C200H-DSC01
Data Setting
Console
C200H-TC00
0.1 to 49.9 A (with a heater burnout detecting current difference of 2.5 A min.), indication accuracy: 0.5% FS, 1 digit max.
Two points (two loops, each of which consists of a temperature sensor and CT)
PID, ON/OFF (selectable with a switch on the rear panel) (advanced PID with auto-tuning)
Main set value, alarm set value, input shift range, proportional band, integral time, derivative time, sensitivity adjustment, etc.
digit max.
0.0 to 999.9 C/ F (in units of 0.1 C/ F)
0 to 9,999 s (in units of 1 s)
0 to 9,999 s (in units of 1 s)
1 to 99 s (in units of 1 s)
500 ms
--99.9 to 999.9 C/ F (in units of 0.1 C/ F)
Selectable from no alarm function, upper alarm, lower alarm, upper/lower alarm, upper-/lower-range alarm, upper/lower alarm
with standby sequence, upper alarm with standby sequence, lower alarm with standby sequence, absolute-value upper alarm,
or absolute-value lower alarm.
8 banks
5 VDC, 0.33 A max. (supplied from the Backplane)
24 VDC
360 g max.
W225
0.5% of set (designated) value or 2 C whichever larger, 1
+10%

/
--15%
, 200 mA min.
Omron puts accurate temperature control right in the rack to
make advanced PID control with auto-tuning readily accessible.
Eliminates a need for stand-alone controllers with networks.
Display and set parameters with the C200H-DSC01 Data Set-
ting Console. Details on the Data Setting Console are provided
later in this section.
Features
Auto-tuning of PID constants
The temperature controller accepts inputs from a
thermocouple or platinum resistance thermometer. The
module is switch-selectable offering ten different sensor
types.
Transistor, voltage, or current output can be selected as the
control output.
High speed and high accuracy temperature control is
performed with a sampling period of 500 ms and with an
indication accuracy of 0.5%.
Eight data values such as main set value, alarm set value,
and input shift range can be preset in one data bank and a
maximum of eight data banks can be preset with each bank
preset for a different purpose. It is possible to change the
banks during operation.
Alarm outputs can be selected out of ten modes, such as an
upper limit, lower limit, and upper/lower limit.
The heater current is monitored by the high-precision current
transformer (CT) capable of detecting in 0.1 A units. Through
the use of heater burnout detection, heater burnout can be
quickly detected.
Data input and process value monitoring -- using the Data
Setting Console.
C200H-TC10
digit max.
0.5% of set (designated) value or 1 C whichever larger, 1


Related parts for C200H-DA001