C200H-DA001 Omron, C200H-DA001 Datasheet - Page 81

no-image

C200H-DA001

Manufacturer Part Number
C200H-DA001
Description
2PT-D/A:12-BIT
Manufacturer
Omron
Datasheet

Specifications of C200H-DA001

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
78
COMMUNICATIONS MODULES
SYSMAC LINK MODULES
C200HW-SLK23/24
(Coaxial cable)
Communications Board
C200HW-COM01
C200HW-COM04-E
(w/RS-232C port)
Bus Connection Unit
C200HW-CE001
(for 1 Module)
C200HW-CE002
(for 2 Modules)
C200H-APS03
Optional Power Supply Module
C200HW-SLK13/14
(Fiber-optic)
SYSMAC LINK is a fiber-optic token ring network designed to
transfer large amounts of control data in real-time between
PLCs. Both coaxial and fiber-optic medias may be used.
The C200H SYSMAC Link Modules are easily integrated to
the C200H CPU. The Modules connect to the CPU through
one of the C200HW-COM01/COM04-E Communications
Boards with a C200HW-CE001/CE002 Bus Connector.
Features
Optional Power Supply Module
The SYSMAC Link Modules are designed to receive back-up
power supply from the Optional Power Supply Module. Should
any failure of the SYSMAC Link Module occur, the node bypass
function will activate to prevent shutdown of the entire network.
Note: Mount the SYSMAC LINK Module to the left of the CPU.
Maximum of 62 SYSMAC LINK Modules -- Up to 62
SYSMAC LINK Modules can be connected in one network. In
addition, two SYSMAC LINK Modules can be mounted on
one PLC, allowing multi-level system configuration.
Data Modules -- The data link capacity is as large as 2,966
words. High-speed and large-capacity data communications
are possible using the LR area and DM area.
Flexible Data Link configuration -- Since an optimum data link
table can be created for each node (Machine No.) using the
SYSMAC Support or SYSWIN, the data link area can be
used effectively.
Event communications -- using the SEND and RECV
instructions, up to 256 words of data can be sent or received
for any node in the network.
Remote programming or monitoring using the SYSMAC
Support Software -- Programs can be transferred to any
SYSMAC Module within the network and various monitoring
operations can be performed for that Module.
Built-in LSI exclusively for communications -- The built-in LSI
allows setting of the communication time period between
SYSMAC Modules. The control station is automatically
switched when any trouble occurs in the data link control
station, assuring a highly reliable data link system.
The SYSMAC LINK Module cannot be used with the
C200HE-CPU11-E.