990XCP98000

Manufacturer Part Number
990XCP98000
Description
QUANTUM CPU BATTERY FOR S
Manufacturer
SQUARE D
Datasheet

Specifications of 990XCP98000

Rohs Compliant
YES
Battery Capacity
1800mAh
Battery Technology
Lithium
Battery Voltage
3V
Battery Terminals
Connector
Weight
0.12lb
10
10
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
Characteristics
Functional safety certification
Approvals
Number of channels
I/O addressing
TC thermocouple types
and ranges
Low level ranges
TC resistance/max. source resistance
Input impedance
Input filter
Normal noise rejection
Cold junction compensation (CJC)
Resolution
Thermocouple absolute
accuracy
Millivolt absolute
accuracy
Isolation
Total update time
Fault detection
Bus current required
Power dissipation
External power supply
Input module characteristics (continued)
Type of module
4/50
J
K
E
T
S
R
B
TC ranges
Millivolt ranges
Types J, K, E, T
Types S, R, B
At 25°C
Accuracy drift acc.
to temperature
Channel-to-channel
Channel-to-bus
(continued)
°C
°C
°C
°C
°C
°C
°C
mV
W
s
mA
W
Modicon
automation platform
Analog I/O modules
(1) The open wire detection device can be disabled on these ranges.
The “Grounding and Electromagnetic Compatibility of PLC Systems. Basic Principles and
Measures. User Manual” no. 33002439 provides helpful information on setting up Modicon
Quantum PLCs in accordance with the directives and legal regulations in force in the
European Union and North America.
140 ATI 030 00
UL 508, CSA 22.2-142, FM Class 1 Div.2, e
8
10 input words
- 210...+ 760
- 270...+ 1370
- 270...+ 1000
- 270...+ 400
- 50...+ 1665
- 50...+ 1665
- 130...+ 1820
- 100...+ 100 (1)
- 25...+ 25 (1)
200 max. for rated accuracy
>1
Single low pass at nominal 20 Hz, plus notch filter at 50/60 Hz
120 dB min. at 50 or 60 Hz
Internal cold junction compensation operates between 0…60°C
The connector door must be closed.
Remote cold junction compensation can be set up by connecting a thermocouple (that monitors
the junction block temperature) to channel 1. J, K, and T thermocouples are recommended for
remote cold junction compensation.
1°C (default), 0.1°C, 1°F, 0.1°F
100 mV range, 3.05 µV (16 bits)
25 mV range, 0.76 µV (16 bits)
± 2°C plus ± 0.1% of reading
± 4°C plus ± 0.1% of reading
± 20 µV ± 0.1% of reading
0.15 µV/°C + 0.0015% of reading/°C max.
220 V a at 47...63 Hz or 300 V c max.
1780 V a at 47...63 Hz for 1 minute or 2500 V c for 1 minute
1
8 red LEDs to indicate scale overrun or broken wire conditions
280
1.5
Not required
®
Quantum