990XCP98000 SQUARE D, 990XCP98000 Datasheet - Page 188

no-image

990XCP98000

Manufacturer Part Number
990XCP98000
Description
QUANTUM CPU BATTERY FOR S
Manufacturer
SQUARE D
Datasheet

Specifications of 990XCP98000

Rohs Compliant
YES
Battery Capacity
1800mAh
Battery Technology
Lithium
Battery Voltage
3V
Battery Terminals
Connector
Weight
0.12lb
10
10
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
Presentation,
description
5/4
1
2
3
4
5
6
Modicon
automation platform
Intrinsically safe I/O modules
The Quantum automation platform supports a full range of intrinsically safe
I/O modules designed to interface with a wide variety of sensors or actuators.
Intrinsic safety is a technique that helps to ensure that electrical energy supplied to
circuits in a hazardous area is too low to ignite volatile gases, either from a spark or
from heat release. Intrinsically safe circuits use energy-limiting devices, known as
intrinsically safe barriers, to prevent excessive electrical energy from being applied
to electrical equipment located in hazardous areas. These galvanically isolated
barriers prevent the module from releasing sufficient energy to ignite volatile gases
or vapors in the hazardous area.
Galvanic isolation, in the form of opto-isolators and DC/DC converters, is provided
between the field side output circuitry and the Quantum bus circuitry. The DC/DC
converters provide intrinsically safe power to devices located in hazardous areas.
No external power is required where these modules are installed.
Intrinsically safe I/O modules are designed to fit onto standard Quantum racks.
They can be mounted in any slot position on any Quantum 140 XBP 0pp 00 rack
(3…16 positions).
Each intrinsically safe I/O module requires an I/O connector (140 XTS 332 00).
The connector is color-coded blue to identify it as an intrinsically safe connector.
These connectors are keyed to prevent the wrong connector from being applied to
the module.
The wiring between the intrinsically safe I/O modules and the devices located in the
hazardous area must be separated from other wiring.
This separation can be achieved by either:
b
b
other wiring
b
wiring. With this method, the wiring must be tied in separate bundles to maintain the
required separation.
The 140 AII/AIO/DII/DIO 330 p0 intrinsically safe module front panel comprises:
1
2
3
4
To be ordered separately:
b
grounding kit can also be used to secure cables in installations subject to severe
vibration.
5
6
The “Grounding and Electromagnetic Compatibility of PLC Systems. Basic Principles and
Measures. User Manual” no. 33002439 provides helpful information on setting up Modicon
Quantum PLCs in accordance with the directives and legal regulations in force in the
European Union and North America.
Presentation
I/O connectors
Wiring recommendations
Description
Separate trunking, wiring ducts, or conduits, color-coded blue
Grounded metal or insulated partitions between the intrinsically safe wiring and
Two inches (50 mm) of air space between the intrinsically safe wiring and other
Grounding of the cable shielding is mandatory. The optional
Model number and color code.
A display block with LEDs.
A removable, hinged door and customizable identification label.
A screw connection block with 40 terminals (to be ordered separately).
Optional STB XSP 3000 grounding kit.
STB XSP 3010 terminals for cables with a cross-section of 1.5…6 mm
STB XSP 3020 terminals for cables with a cross-section of 5…11 mm
®
Quantum
STB XSP 3000
2
.
2
or