990XCP98000 SQUARE D, 990XCP98000 Datasheet - Page 443

no-image

990XCP98000

Manufacturer Part Number
990XCP98000
Description
QUANTUM CPU BATTERY FOR S
Manufacturer
SQUARE D
Datasheet

Specifications of 990XCP98000

Rohs Compliant
YES
Battery Capacity
1800mAh
Battery Technology
Lithium
Battery Voltage
3V
Battery Terminals
Connector
Weight
0.12lb
Environmental tests
Voltage and frequency variation
DC voltage variation
Third harmonic
Short interruptions
Voltage dips and pick-ups
Electrical fast transients/Bursts
Hybrid surge
Electrostatic discharge
Radiated electromagnetic field
Conducted interference, induced
by radiated fields
Interference voltage
Field interference
Dry heat
Cold
Damp heat, steady state
Damp heat, cyclic
Cyclic temperature variations
Dry heat when not operating
Cold when not operating
Damp heat when not operating
Thermal shocks when not
operating
Environmental tests
Description of test
Immunity to Low Frequency (L.F.) interference
Description of test
Immunity to High Frequency (H.F.) interference
Electromagnetic emissions
Immunity to climatic variations
Resistance to climatic variations
(e) (1) (2)
IEC/EN 61131-2
IEC/EN 61131-1
IEC/EN 61131-2
IEC/EN 61131-2
IEC/EN 61131-2
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-6
IEC 61000-6-4
EN 55011
IEC 61131-2
IEC 61000-6-4
EN 55011
IEC 61131-2
IEC 60068-2-2 Bd
IEC 60068-2-1 Ad
IEC 60068-2-30 Ca
IEC 60068-2-3 Db
IEC 60068-2-14 Nb
IEC 60068-2-2 Bb
IEC 60068-2-1 Ab
IEC 60068-2-30 Db
IEC 60068-2-14 Na
Standards
Standards
(e) (1)
(e) (1)
Modicon
automation platform
Standards, certifications and
environmental conditions
Un: nominal voltage
Fn: nominal frequency
Udl: undervoltage detection level
(e): tests required by the e European Directives and based on standard IEC/EN 61131-2.
(1) Devices must be installed and wired in accordance with the instructions in the “Grounding and
(2) These tests are carried out with no enclosure, with the devices fixed on a metal grid and
(3) Refer to note (1) at the bottom of page 10/2.
Levels
0.9/1.10 Un; 0.95/1.05 Fn for 30 min
0.8 Un/0.9 Fn for 5 s; 1.2 Un/1.1 Fn for 5 s
0.85 Un...1.2 Un for 30 min with 5% ripple (peak values)
10% Un; 0°/5 min...180°/5 min
10 ms with power supply a; 1 ms with power supply c
Un-0-Un; Un for 60 s; 3 separate cycles of 10 s
Un-0-Un; Un for 5 s; 3 separate cycles of 1 to 5 s
Un-0.9 Udl; Un for 60 s; 3 separate cycles of 1 to 5 s
Levels
a/c power supply: 2 kV in wired mode/common mode
Discrete I/O > 48V: 2 kV in common mode; other ports: 1 kV in common mode
2 kV between shielding and ground
4 kV contact, 8 kV air
10 V/m; 80 MHz...2 GHz
Sinusoidal amplitude modulation 80%/1 kHz
3 V: 0.15 MHz...80 MHz
Sinusoidal amplitude modulation 80%/1 kHz
Class A
150 kHz...500 kHz quasi-peak 79 dB (µV); average 66 dB (µV)
500 kHz..0.30 MHz quasi-peak 73 dB (µV); average 60 dB (µV)
Class A, measurement at 10 m
30 MHz...230 MHz quasi-peak 40 dB (µV); 230 MHz...1 GHz quasi-peak 47 dB (µV)
60°C for 16 h
0°C for 16 h
60°C with 93% relative humidity/96 h
[55°C (E.O)] - 25°C with 93...95% relative humidity; 2 cycles: 12 h/12 h
0...60°C/5 cycles: 6 h/6 h (3)
85°C for 96 h
-40°C for 96 h
25...60°C with 93...95% relative humidity; 2 cycles: 12 h/12 h
-40...85°C; 2 cycles: 3 h/3 h
electromagnetic compatibility with PLCs” manual, electronic version in PDF format supplied
on CD-ROM with the Unity Pro
UNY USE 909 CD M (see page 7/39).
wired in accordance with the recommendations in the manual.
®
Quantum
software packages or included on DVD reference
10/3
0
10
1
2
3
4
5
6
7
8
9

Related parts for 990XCP98000