6-2-4 Errors in the System Installer Mode and Their Remedies
418
Responding to Displayed Error Messages
System Program not exist or
incorrect.
Unable to erase System
Program.
Unable to download System
Program.
Unable to write System Settings.
Unable to erase Screen Data.
Message
This section describes the errors that may occur in the System Installer mode of
the PT, and the remedies for these errors.
- The system program has not
- The system program has been
Hardware fault, or flash memory
(memory for storing the system
program) has reached its life.
- A communication error
- Illegal data has been written
- Hardware fault, or flash
Hardware fault, or flash memory
(memory for storing the system
program) has reached its life.
Hardware fault, or flash memory
(memory for storing the system
program) has reached its life.
been installed.
deleted due to a hardware
fault, or because the flash
memory (memory for storing
the system program) has
reached its life.
occurred during downloading
of the system program.
into the screen data memory.
memory (memory for storing
the system program) has
reached its life.
Cause
Select Download System Program and
download the system program. (Refer to
Clearing/Installing the System Program in
section 6 in the Setup Manual .)
If this does not solve the problem, contact your
OMRON service center.
If the same message is displayed on repeating
selection of Download System Program and
attempting to delete the system program several
times, contact your OMRON service center.
(Refer to Clearing/Installing the System Program
in section 6 in the Setup Manual .)
Select Download System Program and
download the system program again. (Refer to
Clearing/Installing the System Program in
section 6 in the Setup Manual .)
Also refer to 6-2-3 Errors Occurring on Screen
Data Initialization and Transmission (page 417),
and take the corrective action described for tool
transmission errors.
If this does not solve the problem, contact your
OMRON service center.
If the same message is displayed on repeating
writing of system settings several times, contact
your OMRON service center.
If writing is normally terminated after the error
message was once displayed, the Memory
Switch setting for system program may have
been altered. In such a case, check and re-set
the setting in the Memory Switch menu of the
Maintenance mode.
If the same message is displayed on repeating
screen data deletion several times, contact your
OMRON service center.
Remedy
Section
6-2