Wiring Methods
2. Do not connect bare stranded wires directly to terminals.
• Confirm that the Units have been mounted properly.
• Do not remove the protective label from the top of the Unit until wiring has
• Remove the label after wiring has been completed to allow air circulation
• Wire the Units so that they can be easily replaced.
• In addition, make sure that the I/O indicators are not covered by the wir-
• Do not place the wiring for I/O Units in the same duct or raceway as power
• Tighten the terminal screws to the torque of 0.8 N m.
been completed. This label prevents wire strands and other foreign matter
from entering the Unit during wiring procedures.
needed for cooling.
ing.
lines. Inductive noise can cause errors in operation.
During wiring
Screw (3.5 mm screw with
self-raising pressure plate)
After wiring
Remove the label.