CS1D-II102D Omron, CS1D-II102D Datasheet - Page 566

no-image

CS1D-II102D

Manufacturer Part Number
CS1D-II102D
Description
CS1D Dual IO Interface Unit
Manufacturer
Omron
Datasheet

Specifications of CS1D-II102D

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Auxiliary Area Allocations
A402
A403
A404
A405
Words
Address
A40215
A40300
to
A40308
A40309
A40310
A40400
to
A40407
A40408
to
A40415
A40515
Bits
FAL Error
Flag
(Non-fatal
error)
Memory
Error
Location
Memory
Card
Start-up
Transfer
Error Flag
Flash
Memory
Error
I/O Bus
Error Slot
Number
I/O Bus
Error Rack
Number
Peripheral
Servicing
Too Long
Flag (Sin-
gle CPU
Systems
onl7)
Name
ON when a non-fatal error is gener-
ated by executing FAL(006). The
CPU Unit will continue operating and
the ERR/ALM indicator on the front
of the CPU Unit will flash.
The bit in A360 to A391 that corre-
sponds to the FAL number specified
in FALS(006) will be turned ON and
the corresponding error code will be
written to A400. Error codes 4101 to
42FF correspond to FAL numbers
001 to 2FF (0 to 511).
(This flag will be turned OFF when
the error is cleared.)
When a memory error occurs, the
Memory Error Flag (A40115) is
turned ON and one of the following
flags is turned ON to indicate the
memory area where the error
occurred.
A40300: User program
A40304: PLC Setup
A40305: Registered I/O Table
A40307: Routing Table
A40308: CPU Bus Unit Settings
When a memory error occurs, the
CPU Unit will continue operating and
the ERR/ALM indicator on the front
of the CPU Unit will flash.
(The corresponding flag will be
turned OFF when the error is
cleared.)
ON when automatic transfer at start-
up has been selected and an error
occurs during automatic transfer. An
error will occur if there is a transfer
error, the specified file does not
exist, or the Memory Card is not
installed.
(This flag will be turned OFF when
the error is cleared by turning the
power off. The error cannot be
cleared without turning the power
off.)
Turns ON when the flash memory
fails.
Contains the 8-bit binary slot num-
ber (00 to 08) where an I/O Bus
Error occurred.
CPU Unit operation will stop and the
ERR/ALM indicator on the front of
the CPU Unit will light. The I/O Bus
Error Flag (A40114) will be ON.
(This flag will be turned OFF when
the error is cleared.)
Contains the 8-bit binary rack num-
ber (00 to 07) where an I/O Bus
Error occurred.
CPU Unit operation will stop and the
ERR/ALM indicator on the front of
the CPU Unit will light. The I/O Bus
Error Flag (A40114) will be ON.
(This flag will be turned OFF when
the error is cleared.)
Turns ON when the peripheral ser-
vicing time in a Parallel Processing
Mode exceeds 2 s. This will also
cause a cycle time error and opera-
tion will stop.
Function
ON: FALS(006)
error occurred
OFF: FALS(006)
not executed
ON: Error
OFF: No error
ON: Error
OFF: No error
ON: Error
OFF: No error
00 to 08 hex
(slot No. 0 to 8)
00 to 03 hex
(Rack No. 0 to 3)
1: Too long (Par-
allel processing
cannot be used.)
0: Not too long
(Parallel pro-
cessing can be
used.)
Settings
Cleared
Cleared
Cleared
Clear
Cleared
Cleared
Cleared
change
Status
mode
after
Cleared
Cleared
Cleared
Clear
Cleared
Cleared
Cleared
Status at
startup
When
error
occurs
---
When
power is
turned ON
When
error
occurs
---
---
Written
when
error
occurs
Timing
Appendix B
A360 to
A391,
A400
A40115
---
A40114
A40114
A268
settings
Related
flags,
531

Related parts for CS1D-II102D