Specifications of CS1D-II102D

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Auxiliary Area Allocations
A320
A322
A324
Words
Address
Error Power Supply Unit Location
When the voltage on the primary side of the Power Supply Unit drops or is interrupted, one of the following bits will turn ON to
show the location of the Power Supply Unit with the error. A31602 (Duplex Power Supply Unit Error Flag) can be used to deter-
mine if there is an error and the following bits can be used to locate the error.
A32000
A32001
A32002
A32003
A32004
A32005
A32006
A32007
A32008
A32009
A32010
A32011
A32012
A32013
A32014
A32015
CPU Standby Information
A32203
A32204
A32205
A32206
A32207
A32208
A32406
A32407
A32411
A32413
Bits
Right Power Supply Unit on CPU Rack (Rack 0)
Left Power Supply Unit on CPU Rack (Rack 0)
Right Power Supply Unit on CPU Rack (Rack 1)
Left Power Supply Unit on CPU Rack (Rack 1)
Right Power Supply Unit on CPU Rack (Rack 2)
Left Power Supply Unit on CPU Rack (Rack 2)
Right Power Supply Unit on CPU Rack (Rack 3)
Left Power Supply Unit on CPU Rack (Rack 3)
Right Power Supply Unit on CPU Rack (Rack 4)
Left Power Supply Unit on CPU Rack (Rack 4)
Right Power Supply Unit on CPU Rack (Rack 5)
Left Power Supply Unit on CPU Rack (Rack 5)
Right Power Supply Unit on CPU Rack (Rack 6)
Left Power Supply Unit on CPU Rack (Rack 6)
Right Power Supply Unit on CPU Rack (Rack 7)
Left Power Supply Unit on CPU Rack (Rack 7)
CPU Bus/
Special I/O
Unit Star-
tup Flag
Duplex
Bus Error
Standby
Flag
Duplex
Verifica-
tion Error
Standby
Flag
Waiting for
Other CPU
Unit
Standby
Flag
Inner
Board
Startup
Flag
Expan-
sion Power
OFF
Standby
Flag
Inner
Board
Error
Flags
(Non-fatal
error)
(Duplex
CPU Sys-
tem only)
Right/Left
CPU Unit
Battery
Error
Flags
(Duplex
CPU Sys-
tem only)
Name
ON: The CPU Unit is on standby
waiting for CPU Bus or Special I/O
Units to start.
ON: The CPU Unit is on standby
because a duplex bus error occurred
at startup. (Duplex CPU System
only)
ON: The CPU Unit is on standby
because a duplex verification error
occurred at startup. (Duplex CPU
System only)
ON: The CPU Unit is on standby
waiting for the other CPU Unit to
start operation at startup. (Duplex
CPU System only)
ON: The CPU Unit is on standby
waiting for an Inner Board to start.
(Single CPU Systems or Process-
control CPU Units only)
ON: The CPU Unit is on standby
because power is not being supplied
to an Expansion Rack.
ON if A40208 turns ON for the right
Inner Board.
ON if A40208 turns ON for the left
Inner Board.
ON if A40204 is ON in the right CPU
Unit.
ON if A40204 is ON in the left CPU
Unit.
Function
ON: Primary-
side input power
error
OFF: Normal
ON: Standby
OFF: Other
ON: Non-fatal
Inner Board
Error
OFF: Normal
ON: Battery
error
OFF: Normal
Settings
Cleared
Held
Cleared
Cleared
change
Status
mode
after
Cleared
Cleared
Cleared
Cleared
Status at
startup
When
error
occurs
When
CPU Unit
goes on
standby
When
error
occurs
When
error
occurs
Timing
Appendix B
A31602
---
A402
A402
A402
settings
Related
flags,
517