CS1D-II102D Omron, CS1D-II102D Datasheet - Page 579

no-image

CS1D-II102D

Manufacturer Part Number
CS1D-II102D
Description
CS1D Dual IO Interface Unit
Manufacturer
Omron
Datasheet

Specifications of CS1D-II102D

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Note In CS1D PLCs, the following flags are provided in a special read-only area and can be specified with the
544
Auxiliary Area Allocations
A803
A804
Condition Code
Area
Word
Addresses
Flag area
labels given in the table. These flags are not contained in the Auxiliary Area.
---
A80300
A80301
A80302
A80303
---
A80400
A80401
A80402
A80403
A80404
Bit
Online
Replace-
ment
Comple-
tion Error
Details
Details on
duplex
verifica-
tion error
caused by
different
unit ver-
sions
Error Flag
Access Error Flag
Carry Flag
Greater Than Flag
Equals Flag
Less Than Flag
Negative Flag
Overflow Flag
Underflow Flag
Greater Than or Equals
Flag
Not Equal Flag
Less than or Equals Flag <=
Always ON Flag
Always OFF Flag
Name
Name
When an online replacement function
failed, the relevant flag will be turned
ON.
No Unit mounted or Unit mounted in
another slot.
Replaced Unit and new Unit are differ-
ent models.
Different unit numbers on replaced and
new Units.
Different node numbers on replaced
and new Units (when replacing a
duplex Communications Unit).
The corresponding bit is turned ON
when a duplex verification error
occurred due to different unit versions.
Ethernet Duplex Setting Flag (PLC
Setup)
Unit Removal without a Programming
Device Function Setting Flag (PLC
Setup)
Removal/Addition of Units without a
Programming Device Setting Flag (PLC
Setup)
Turn ON Error Unit Number Flag when
Removing a Special Unit Setting Flag
(PLC Setup)
Communications Port Auto-allocation
Instruction (Instruction)
Function
ER
AER
CY
>
=
<
N
OF
UF
>=
<>
A1
A0
Label
Turns ON when an error occurs in processing an instructions, indi-
cating an error end to the instruction.
Turns ON when an attempt is made to access an illegal area. The
status of this flag is maintain only during the current cycle and only
in the task in which it occurred.
Turns ON when there is a carry or borrow in a math operation,
when a bit is shifted into the Carry Flag, etc.
Turns ON when the result of comparing two values is “greater
than,” when a value exceeds a specified range, etc.
Turns ON when the result of comparing two values is “equals,”
when the result of a math operation is 0, etc.
Turns ON when the result of comparing two values is “less than,”
when a value is below a specified range, etc.
Turns ON when the MSB in the result of a math operation is 1.
Turns ON when the result of a math operation overflows.
Turns ON when the result of a math operation underflows.
Turns ON when the result of comparing two values is “greater than
or equals.”
Turns ON when the result of comparing two values is “not equal.”
Turns ON when the result of comparing two values is “less than or
equals.”
This flag is always ON.
This flag is always OFF.
OFF
Online replace-
ment failed.
ON: Mismatch
OFF: Match
Settings
ON:
Held
Held
change
Status
mode
Meaning
after
Status at
Cleared
Cleared
startup
---
When
duplex
verifica-
tion error
occurs
Timing
Appendix B
A80115
A31600,
A317
Settings
Related
Flags,