CS1D-II102D Omron, CS1D-II102D Datasheet - Page 570

no-image

CS1D-II102D

Manufacturer Part Number
CS1D-II102D
Description
CS1D Dual IO Interface Unit
Manufacturer
Omron
Datasheet

Specifications of CS1D-II102D

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Auxiliary Area Allocations
A436
A437
A439
A440
Words
Address
A43600
to
A43615
A43700
to
A43715
A43915
All
Bits
Duplex
Communi-
cations
Switched
Flags
(non-fatal
communi-
cations
error)
Duplex
Communi-
cations
Standby
Unit Error
Flags
(non-fatal
communi-
cations
error)
Duplex Ini-
tialization
Flag
(Duplex
CPU Sys-
tems only)
Max. Inter-
rupt Task
Process-
ing Time
(Single
CPU Sys-
tems only)
Name
Active/Standby Communications
Units
ON: An error was detected in self-
diagnosis in the active Communica-
tions Unit and operation was
switched to the standby Communi-
cations Unit. Communications will
be continued by the standby Com-
munications Unit.
Primary/Secondary Communica-
tions Units (See Note)
ON: An error was detected in self-
diagnosis in the primary Communi-
cations Unit and operation was
switched to the secondary Commu-
nications Unit. Communications will
be continued by the secondary
Communications Unit.
All Communications Units
Bits 00 to 15 correspond to unit
numbers 0 to F.
This flag is turned OFF when online
Unit replacement is performed for
the faulty Communications Unit.
Note: Primary/Secondary Commu-
Active/Standby Communications
Units
ON: An error was detected in self-
diagnosis in the standby Communi-
cations Unit. Communications will
be continued by the active Commu-
nications Unit.
Primary/Secondary Communica-
tions Units (See Note)
ON: An error was detected in self-
diagnosis in the secondary Commu-
nications Unit. Communications will
be continued by the primary Com-
munications Unit.
All Communications Units
Bits 00 to 15 correspond to unit
numbers 0 to F.
This flag is turned OFF when online
Unit replacement is performed for
the faulty Communications Unit.
Note: Primary/Secondary Commu-
ON: Duplex operation being initial-
ized.
Contains the Maximum Interrupt
Task Processing Time in units of
0.1 ms.
(This value is written after the inter-
rupt task with the max. processing
time is executed and cleared when
PLC operation begins.)
nications Units are supported
by CPU Unit Ver. 1.1 or later.
nications Units are supported
by CPU Unit Ver. 1.1 or later.
Function
ON: Duplex
Communica-
tions Units
switched
OFF: Normal
ON: Error
OFF: Normal
0000 to FFFF
hexadecimal
Settings
Held
Held
Cleared
Cleared
change
Status
mode
after
Cleared
Cleared
Cleared
Cleared
Status at
startup
When
communi-
cations
are
switched
to sim-
plex oper-
ation
When
error
occurs in
Communi-
cations
Unit
---
See Func-
tion col-
umn.
Timing
Appendix B
A40214
A31603
A042 to
A049
A40214
A31603
A32808
---
settings
Related
flags,
535

Related parts for CS1D-II102D