5384 3M Interconnect Solutions, 5384 Datasheet

no-image

5384

Manufacturer Part Number
5384
Description
Manufacturer
3M Interconnect Solutions
Datasheet

Specifications of 5384

Lead Free Status / Rohs Status
Supplier Unconfirmed
Kit Contents
3—Lug Covers
3—Cold Shrink Terminations
12—Mastic Sealing Strips
3—Copper Tape Strips
3—Cleaning Kits
6—Tubes Silicone Grease
3—Cold Shrink Jacket Tubes
3—Constant Force Springs
Technical Information:
• For shielded (Tape, Wire or UniShield
• Cable Size Range: Feeder: #8 AWG–500 kcmil
• Copper Conductors
Motor Lead Pigtail or V-Stub Splice
5380 Series
For 5/8 kV Non-Shielded and Shielded Feeder Cables (Tape, Wire or
UniShield
Instructions
 CAUTION
Working around energized systems may cause serious
injury or death. Installation should be performed by
personnel familiar with good safety practice in handling
electrical equipment. De-energize and ground all electri-
cal systems before installing product.
Number
and non-shielded cables
5381
5382
5383
5384
Kit
250 – 500
1/0 – 250
Feeder
2 – 1/0
Cable Size Range
8 – 4
(AWG/kcmil)
®
Cables)
Motor Lead: #10 AWG–500 kcmil
4/0 – 500
2 – 250
4 – 1/0
Motor
10 – 4
Lead
0.53 – 0.88" (13,5–22,4 mm)
0.43 – 0.65" (11–16,5 mm)
0.75 – 1.12" (19–28,4 mm)
0.30 – 0.51" (7,6–13 mm)
Feeder Cable Insulation
®
)
O.D. Range
Table 1
3—Cable Ties
3—Ground Straps
1—Instruction Sheet
Requires Vinyl Tape that is not in kit
Note: Visually inspect all components. If any
component is missing or appears damaged, do not
install. Call customer service at 1-800-245-3573 for a
replacement product.
V-Stub Termination or
1 1/4" (32 mm)
1 1/2" (38 mm)
5/8" (16 mm)
3/4" (19 mm)
For 5/8 kV Non-Shielded and
Pigtail Splice Kits
Max. Bolt
5381, 5382, 5383, 5384
3M
Length
78-8126-9102-6-B
Shielded Cables
Motor Lead
2 1/2" (63,5 mm)
5 1/2" (140 mm)
2 3/4" (70 mm)
4" (102 mm)
Max. Lug
Length
Size of Cables
0.90" (23 mm)
1.16" (29 mm)
1.60" (41 mm)
2.06" (52 mm)
ID of Boot to

5384 Summary of contents

Page 1

... Table ® V-Stub Termination or Pigtail Splice Kits For 5/8 kV Non-Shielded and 5381, 5382, 5383, 5384 Max. Lug ID of Boot to Length Size of Cables 2 1/2" (63,5 mm) 0.90" (23 mm) 2 3/4" (70 mm) 1.16" (29 mm) 4" (102 mm) 1.60" ...

Page 2

Instructions for 5/8 kV Non-Shielded Feeder Cables A. Prepare Cable According to Standard Procedures Note: The terminations and grounding components will not be used for non-shielded cable. 1. Check to be sure cables fit within cable kit range as shown ...

Page 3

Install Lug Cover. Position Lug Cover so the punched holes are positioned between the cables (Figure 3). Note: The kit contains a small tube of Silicone Grease. Use it to lightly lubricate the mastic and vinyl tape wraps. This ...

Page 4

For Shielded Motor Lead Cable (if connection grounded, see next section) For Tape Shielded Cable see Figures 4a and 5a. For Wire Shielded Cable see Figures 4b and 5b. For UniShield® Cable see Figures 4c and 5c. ...

Page 5

B. Install Termination 1. Install silicone grease at semi-con step and on cable insulation. Note: Termination is in bag with copper tape strip. 2. Install termination beginning at cable jacket edge for tape or wire shielded cables. For UniShield® cables, ...

Page 6

C. Install Lugs 1. Install and crimp lugs per manufacturer's direction; see back page Bolt lugs together. See Table 1 on cover for maximum bolt length. See Figure 6 for proper bolt/lug arrangement. Figure 6 D. Install ...

Page 7

Instructions for 5/8 kV Shielded Feeder Cables (Tape, Wire Shielded or UniShield A. Prepare Cable According to Standard Procedures 1. Check to be sure cables sizes fit within cable kit range as shown in Table 1 on cover. For Non-Shielded ...

Page 8

Position pre-formed ground braid with short tail over tape shield directly adjacent to cable jacket cut edge. Position long tail of ground braid, extending over cable jacket with solder block over mastic strip (Figure 11). Secure ground braid to ...

Page 9

Wrap two half-lapped layers of vinyl tape around mastic seal, constant force spring and onto tape shield 1/2" (13 mm) (Figure 13). SPECIAL NOTE FOR CLOTH OR PAPER SEMI-CON INSULATION SHIELD In cables with cloth or paper semi-conductive shields, ...

Page 10

Select one mastic strip from kit and remove white release liners. Using light tension, apply a single wrap of mastic around the cable jacket 1/4" (6 mm) from cut edge (Figure 16). Cut off excess. Figure 16 ����� ������ ...

Page 11

Wrap two half-lapped layers of vinyl tape around mastic seal, constant force spring and 1/2" (13 mm) onto shield wires (Figure 19). SPECIAL NOTE FOR CLOTH OR PAPER SEMI-CON INSULATION SHIELD In cables with cloth or paper semi-conductive shields, ...

Page 12

Remove constant force spring. Bend shield wires back upon cable jacket 3" (76 mm). Cut excess shield wire and discard (Figure 22). Figure 22 �� ��� ��� 22. Remove semi-conductive jacket to dimension shown in Figure 23. Note: To ...

Page 13

Position pre-formed ground braid with short tail directly over cut edge of folded back shield wires. Position long tail of ground braid, extending over cable semi-conductive jacket with solder block over mastic strip (Figure 25). Secure ground braid to ...

Page 14

Install Cold Shrink jacket tube beginning 1" (25 mm) from end of semi-con (Figure 28). Figure 28 ������ ����������������� ������ ����� �������� ����� ���� Instructions for 5/8 kV Pigtail Shielded Feeder Cables with Ground (Ribbon, Wire Shielded or UniShield ...

Page 15

D. Install Lug Cover 1. Separate cables and apply mastic strip between and around them, (Figure 31). Mastic will be on end of termination and cold shrink jacketing tube. Build mastic to an overall diameter that is greater than the ...

Page 16

... Therefore, the published 3M warranty does not extend to any 3M connectors crimped in tools not made by 3M. The warranty on 3M Scotchlok splicing tools can also be voided if used on non-3M connectors. ...