5384 3M Interconnect Solutions, 5384 Datasheet - Page 14

no-image

5384

Manufacturer Part Number
5384
Description
Manufacturer
3M Interconnect Solutions
Datasheet

Specifications of 5384

Lead Free Status / Rohs Status
Supplier Unconfirmed
28.
B.
1.
Note: Termination is in bag with copper tape strip.
2.
C.
1.
2.
Figure 28
Figure 29
Figure 30
Install Cold Shrink jacket tube beginning 1" (25 mm) from end of semi-con (Figure 28).
Install Termination
Install silicone grease at semi-con step and on cable insulation.
Install termination beginning at jacket tube edge (Figure 29).
Install Lugs
Install and crimp lugs per manufacturer's direction; see back page if 3M
Bolt lugs together. See Table 1 on cover for maximum bolt length. See Figure 30 for proper bolt/lug
arrangement.
Instructions for 5/8 kV Pigtail Shielded Feeder Cables with Ground
����� ����
������ �����
��������
���� ������ ������ ����
����� ���� ��� ��
������ �����������������
�������� �� ��
������� �����
(Ribbon, Wire Shielded or UniShield
���� ������ ������ ����
������ �����
��������
������ �����
��������
����� �� ��� ��� ���� ���
�� ����� ��������
��
14
�����������
���� ������ ������ ����
������ �����������������
������ �����������������
®
Cables)
Lugs are used.
78-8126-9102-6-B