For Non-Shielded Motor Lead Cable
2.
3.
For Shielded Feeder Cable
For Tape Shielded Cable see item #4.
For Wire Shielded Cable see item #13, this section.
For UniShielded Cable see item #20, this section.
4.
5.
6.
7.
Figure 9
Figure 10
78-8126-9102-6-B
Prepare Cable According to Standard Procedures
Check to be sure cables sizes fit within cable kit range as shown in Table 1 on cover.
Remove cable insulation for length recommended by terminal lug manufacturer; if no information is
available, remove for depth of lug barrel.
Clean insulation for approximately 6" using solvent-saturated cloth provided in kit.
For Tape Shielded Cables: Prepare cable by removing jacket and shielding per dimensions as shown in
Figure 9. Apply copper tape strip over tape shield to secure.
Remove cable insulation for length recommended by terminal lug manufacturer; if no information is
available, remove for depth of lug barrel.
Clean cable insulation by using solvent-saturated cloths. Do not allow solvent to touch cable semi-con.
If abrasive must be used to remove imbedded semi-con from cable insulation, use a non-conductive, 120-
grit aluminum oxide, such as in the 3M
Select one mastic strip from kit and remove white release liners. Using light tension, apply a single wrap
of mastic around the cable jacket 1/4" (6 mm) from cut edge (Figure 10). Cut off excess.
Instructions for 5/8 kV Shielded Feeder Cables
����� ������
(Tape, Wire Shielded or UniShield
����� ������
With Ground Connection
��� ���
���� �� ���
� ����
��� ������ ����
���� ������
Cable Prep Kit CC-2 or 3M Abrasive Roll A-3.
7
���� �� ���
������ ����
����� ��������
��� ���
� ����
®
Cables)
����� ����������
����� ��
��������
��� ������