CV500BC051 Omron, CV500BC051 Datasheet - Page 103

no-image

CV500BC051

Manufacturer Part Number
CV500BC051
Description
Programmable Logic Controller
Manufacturer
Omron
Datasheet

Specifications of CV500BC051

Peak Reflow Compatible (260 C)
No
Leaded Process Compatible
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Connection Procedure
78
Wiring
1,2,3...
Note
CS1W-RPT03 (GI)
1. Always use the specified Optical Fiber Cables.
2. Although the Optical Fiber Cables can be distinguished by the markings or
3. The maximum distance between nodes depends on the type of GI cable
Use the following procedure to connect Optical Fiber Cables to a Unit.
1. Attach the mounting bracket to the Unit with the provided screws.
2. Attach the clamp to the mounting bracket so that it clamps the cable(s).
3. Remove the Optical Connector Covers from the Unit’s connectors shown
Wired Controller
Link Unit
color, in order to prevent incorrect connection it is recommended that tags
are attached to the cables.
(core diameter) that is being used.
62.5/125 µ m cable: Max. distance between nodes = 2 km
50/125 µ m cable: Max. distance between nodes = 1 km
in the following diagram if there are covers protecting the connectors.
CS1W-RPT03
Repeater Unit
Send
Receive
SL2
SL1
Clamp
GI cable
2. Attach the clamp to the
mounting bracket so that
the cable(s) are clamped.
Mounting bracket
1. Screw the mounting
bracket to the Unit.
Receive
Send
CS1W-RPT03
Repeater Unit
SL1
SL2
Section 3-3
Wired Controller
Link Unit