Reading an Error Log
Clearing an Error Log
9-4
318
Troubleshooting Error Messages in CX-Net Data Link Table Check
Troubleshooting Error Messages in CX-Net Data Link
Table Check
The Communications Unit’s error log (stored in the Unit’s EEPROM) will be
displayed, showing each error’s Error occurring time, Error code, Detail infor-
mation, and Content of Error.
Send the ERROR LOG READ FINS command (command code 2102) to the
appropriate node. Refer to 6-5-11 ERROR LOG READ.
Send the ERROR LOG CLEAR FINS command (command code 2103) to the
appropriate node. Refer to 6-5-12 ERROR LOG CLEAR.
This section describes the error messages displayed during data link table
checks performed with CX-Net and the required troubleshooting. Perform
data link table checks by selecting Validate Table from the Table Menu in the
CX-Net’s Datalink Component Screen, or when transferring data link tables
(by selecting Online - Transfer to PLC).
Example Display of Error List
Section 9-4