CS/CJ-series, CVM1, and CV-series Controller Link Units
326
Handling Precautions
C200HX/HG/HE
CQM1H Series
C200HX/HG/HE
CQM1H Series
Operating level 0
DM 6400
DM 6400
DM 6400
Operating level 0
DM 6400
1,2,3...
Note CS/CJ-series, CVM1, and CV-series Controller Link Unit data is stored in the
4. Set the node address, baud rate, operating level (front DIP switch,
5. Turn ON only those PLC for which Units were replaced.
6. Set the following software switches on the new Controller Link Unit using
7. Turn off the power again to PLCs for which the Controller Link Unit has
8. If the CPU Unit DIP switch pin 5 of the PLC for which the Controller Link
9. Turn off all nodes in the Controller Link Network.
10. If the Controller Link Support Software can be operated, use it to read the
11. If the data links are not activated automatically, activate the data link from
12. If the Controller Link Support Software can be operated, use it to check
13. Return the software switches set in step 6. in the new Controller Link Unit
14. If DIP switch pin 5 on the CPU Unit was switched from ON to OFF in set
EEPROM of the CPU Unit. For this reason even if the Controller Link Unit is
replaced, on the hardware settings must be made to return all settings to their
previous status. If, however, the CPU Unit is replaced, the data link tables and
routing tables will need to be reset.
1. Turn off all nodes in the Controller Link Network.
2. Detach the communications cables attached to the Controller Link Unit to
Operating level 1
DM 6420
Operating level 1
DM 6420
C200HX/HG/HE only) and the terminating resistance for the new Unit to
the same settings as the previous Unit. (Refer to SECTION 4.)
the Programming Device.
been changed.
Unit has been replaced is ON (automatic transmission), set to OFF (no au-
tomatic transmission.)
network parameters and make sure the Network is operating normally.
the data link startup node.
that the data links are operating normally by monitoring the data link status.
to the following settings using the Programming Device.
Check the above if the Controller Link Support Software can be used.
8., turn the PLC OFF once, return the DIP switch to ON, and turn the power
ON again.
be replaced and remove the Unit.
• Polled node/ polling nodes: ON (polled node)
• EEPROM Clear But: ON (EEPROM Clear)
• Polled node/polling node: OFF (polling node)
• EEPROM Clear Bit: OFF (Do not clear EEPROM)
EEPROM Clear Bit
Polled node/polling node 0: Polling node
EEPROM Clear Bit
Polled node/polling node 0: Polling node
0: Do not clear EEPROM
1: Clear EEPROM
1: Polled node
0: Do not clear EEPROM
1: Clear EEPROM
1: Polled node
– : Other settings
–: Other settings