CV500BC051 Omron, CV500BC051 Datasheet - Page 184

no-image

CV500BC051

Manufacturer Part Number
CV500BC051
Description
Programmable Logic Controller
Manufacturer
Omron
Datasheet

Specifications of CV500BC051

Peak Reflow Compatible (260 C)
No
Leaded Process Compatible
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Checking Data Link Status
When 8-bit Format is Specified (i.e., when using a C200HX/HG/HE, CVM1, CV-series, or CQM1H-series
PLC or when using a CS/CJ-series PLC with the data link status storage format specification in the DM
Parameter Area set to 8-bit format)
(See note 1.)
First status word + 0
First status word + 1
First status word + 2
First status word + 3
First status word + 14
First status word + 15
First status word + 16
First status word + 17
First status word + 27
First status word + 28
First status word + 29
First status word + 30
15
Node 2
Node 4
Node 6
Node 8
to
Node 30
Node 32
Node 34
Node 36
to
Node 56
Node 58
Node 60
Node 62
Note
8
7
1. When the default setting is used for the data link status storage destination,
2. Always 1 for the Controller Link Support Board.
3. Always 0 for the Controller Link Support Board.
4. Even if an offset error occurs, the data link will operate and the node will
Node 1
Node 3
Node 5
Node 7
to
Node 29
Node 31
Node 33
Node 35
to
Node 55
Node 57
Node 59
Node 61
16 words are determined within the status area according to the unit num-
ber setting. When the 8-bit format is specified, therefore, the data that is
reflected will be limited to node addresses 1 to 32.
When data link status is required for node addresses 33 or larger, do not
use the default setting, i.e., specify the first word of the status storage area.
If this is done when an 8-bit format is specified, 31 words will be used as
the status storage area.
participate in the data links. In the node where the offset error occurred,
however, all receive area words will be cleared to 0.
0
15 14 13 12 11 10 9
7
6
5
4
Remaining receive area
(See note 6.)
0: Not remaining
1: Remaining
Insufficient (short) receive
area (See note 5.)
0: Sufficient
1: Insufficient
3
Offset error (See note 4.)
0: Normal
1: Error
2
Data link participation
0: Not in data link or data link inactive
1: In data link
Error: Offset exceeds number of
send words.
Insufficient: Receive area is smaller than
send area. Excess data is truncated; other
data is received.
Remaining: Receive area is larger than
send area. Data is received and remaining
words are cleared.
1
Communications error (data link reception)
0: Normal
1: Error
0
8
PLC's CPU Unit error (See note 3.)
0: Normal
1: Error
PLC status (See note 2.)
0: Inactive (user program not running)
1: Active (user program running)
Section 5-4
159

Related parts for CV500BC051