Memory Areas
Local Data Link Participation Status: CIO 1500 + 25 × (Unit No.) + 6 (See page 302.)
Data Link Status: CIO 1500 + 25 × (Unit No.) + 7 to + 22 (See pages 158, 303.)
When the first data link status word for manually set data link tables or for automatically set data links is not set
or is set to 0, the data link status is stored in the words shown below.
+7
+8
+9
+10
+11
+12
+13
+14
+15
+16
+17
+18
+19
+20
+21
+22
Node 2
Node 4
Node 6
Node 8
Node 10
Node 12
Node 14
Node 16
Node 18
Node 20
Node 22
Node 24
Node 26
Node 28
Node 30
Node 32
Node 1
Node 3
Node 5
Node 7
Node 9
Node 11
Node 13
Node 15
Node 17
Node 19
Node 21
Node 23
Node 25
Node 27
Node 29
Node 31
1: Local node data link participating
0: Local node data link not participating or data link inactive
Remaining receive area
0: Not remaining
1: Remaining
Insufficient (short) receive area
0: Sufficient
1: Insufficient
Offset error
0: Normal
1: Error
Data link participation
0: Not in data link or data link inactive
1: In data link
Communications error (data link reception)
0: Normal
1: Error
PLC's CPU Unit error
0: Normal
1: Error
PLC status
0: Inactive (user program not running)
1: Active (user program running)
Error: Offset exceeds
number of send words.
Remaining: Receive
area is larger than send
area. Data is received
and remaining words
are cleared.
Insufficient: Receive
area is smaller than
send area. Excess data
is truncated; other data
is received.