6-2-2 Errors Occurring During Operation
6-2-3 Errors Occurring on Screen Data Initialization and Transfer
6-2-4 Communication Errors
250
Responding to Displayed Error Messages
Battery Lowered
(At the same time, the
RUN indicator will light in
orange (during operation)
or red (when stopped).)
An illegible message (with
meaningless characters)
is displayed
Initialize System
Program?
System Program
Corrupted
System Program is Not
Downloaded
Setting Error
Area Type and Word Address
Word Address Setting
Error
Word Area of Screen data or PT
Control Area is wrong. Please
confirm Screen Data.
Initialization Error
Message
Message
Message
Voltage of battery in the NT30/30C is
low.
DIP switch SW2 pin 6 on the
NT30/30C is OFF. (The Japanese
system program is installed.)
DIP switch SW2 pin 7 on the
NT30/30C is ON.
The system program cannot be
started up because there is an error
in it.
The system program cannot be
started up because it has been
deleted.
Allocated bits/words set with the
NT-series Support Tool not found
NT series Support Tool not found
at PC.
Hardware fault or screen data
memory life reached
The table below shows the errors that can occur during operation of the
NT30/30C, and their remedies.
The table below shows the errors that can occur when data is written to the
NT30/30C screen data memory, and their remedies.
This section describes the errors relating to communication with the PC that can
occur during operation, and their remedies.
S Operation when a Communication Error Occurs
S Procedure when a Communication Error Occurs
When a communication error occurs, the error message is displayed at the
NT30/30C, and the buzzer sounds. Error messages are displayed when the
Automatic Reset memory switch is set (OFF).
Some error messages are displayed even if the Automatic Reset memory
switch is set (ON).
When an error message is displayed, press the [confirm] touch switch dis-
played on the screen. The screen display will return to the RUN mode.
Cause
Cause
Cause
Change the battery. See Replacing the Battery
(page 253).
Switch OFF the power to the NT30/30C, set DIP
switch SW2 pin 6 to ON, and re-install the system
program.
After selecting No, switch OFF the power to the
NT30/30C, set DIP switch SW2 pin 7 to OFF, and
switch the power back on. DO NOT select Yes.
Install the system program with the NT30/NT30C
System Installer.
The system program has to be re-installed. Contact
your OMRON service center.
After checking the PC area being used, set
correct bits/words.
correct bits/words.
If the same message is displayed even after
executing screen data memory initialization or
screen data transmission several times, contact
your OMRON service center.
Remedy
Remedy
Remedy
Section
6-2