CV500ETN01 Omron, CV500ETN01 Datasheet - Page 112

no-image

CV500ETN01

Manufacturer Part Number
CV500ETN01
Description
Programmable Logic Controller
Manufacturer
Omron
Datasheet

Specifications of CV500ETN01

Peak Reflow Compatible (260 C)
No
Leaded Process Compatible
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Send Mail Status 1, 2 (Ethernet Unit to CPU Unit)
Send Mail Status 1
Send Mail Status 2
DM Area Allocations
m
m+17
15 14 13 12 11 10
15 14 13 12 11 10
The meanings of the items shown in the above diagram are explained on the
following pages. For details regarding the related communications services
shown in the diagram, refer to the indicated sections.
The transmission status of user mail, periodic mail, and error log mail are
stored in this word as shown in the following table.
While mail is being sent, the transmission status of the three bits each for
send condition settings 1 to 8, i.e., bits 02, 01, and 00; bits 06, 05, and 04; or
bits 10, 09, an 08 are 0, 0, and 1 respectively. After the transmission has been
completed normally, they become 0, 1, and 0. If the transmission is ended
with an error, they become 1, 1, and 0.
Check this transmission status in the ladder program as required.
OFF
OFF
OFF
ON
ON
02
06
10
14
9
9
OFF
OFF
ON
ON
ON
Bits
01
05
09
13
8
8
7
7
OFF
ON
OFF
OFF
ON
00
04
08
12
6
6
Mail is either waiting to be sent or can be sent using the Mail
Send Switch. No mail is being sent.
Mail is being sent.
Mail is either waiting to be sent or can be sent using the Mail
Send Switch. The previous mail transmission was completed
normally.
Mail is either waiting to be sent or can be sent using the Mail
Send Switch. An error occurred in the previous mail transmis-
sion.
Mail cannot be sent (system setting error).
5
5
4
4
3
3
2
2
1
1
0
0
Status of Send Condition Setting 1
Status of Send Condition Setting 2
Status of Send Condition Setting 3
Status of Send Condition Setting 4
Status of Send Condition Setting 5
Status of Send Condition Setting 6
Status of Send Condition Setting 7
Status of Send Condition Setting 8
Status
Section 4-2
87