CV500ETN01 Omron, CV500ETN01 Datasheet - Page 88

no-image

CV500ETN01

Manufacturer Part Number
CV500ETN01
Description
Programmable Logic Controller
Manufacturer
Omron
Datasheet

Specifications of CV500ETN01

Peak Reflow Compatible (260 C)
No
Leaded Process Compatible
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Setup
Destination IP Address
(Change Dynamically)
Baud Rate
TCP/IP keep-alive
IP Address Table
IP Router Table
FTP
Item
Login
Password
Port No.
Note
Select to dynamically change the remote (destination) IP address for
FINS/UDP. To prohibit dynamic changes, deselect this box.
Select the Ethernet baud rate for the Ethernet Unit.
Select either automatic detection or 10Base-T. (For 100Base-TX, select
automatic detection.)
Set the liveness-checking interval. When socket services using either
FINS/TCP or TCP/IP are used, the connection will be terminated if there
is no response from the remote node (either a server or client) within the
time set here. (Enabled for socket services using FINS/TCP or TCP/IP
only.)
Setting range: 0 to 65,535 minutes
This setting applies to the keep-alive setting for each connection set
with the FINS/TCP tab.
Set the IP address table that defines the relationship between FINS
node addresses and IP addresses.
With FINS/UDP, this is enabled only when the IP address table method
is set as the IP address conversion method.
Set when the Ethernet Unit is to communicate through the IP router with
nodes on another IP network segment.
Sets the login name for connecting to the Ethernet Unit by FTP.
Sets the password for connecting to the Ethernet Unit by FTP.
Set the FTP port number for the Ethernet Unit.
There is normally no need to change this number.
Two ports are used for FTP: a control port and a data transfer port. This
setting sets only the control port, and then the data transfer port uses
the number that is one less than the control port.
(1) The setting to enable or disable dynamic changing of remote IP address-
(2) Make settings using the unit settings function in the CX-Programmer (to
es is available for Ethernet Units with Unit Ver. 1.3 or later.
be included in version 5.0 and higher) or using the Web function (refer to
Appendix G Ethernet Unit Web Function).
Contents
Checked
(Change Dynami-
cally)
Auto
0
(120 minutes)
None
None
None
None
(“CONFIDENTIAL”)
0
(Number 21 is
used.)
Section 3-1
Default
63