Error Log Table
Error Log Location
FINS Commands for Error
Logs
8-3-1
Error Log
0001
0002
0006
000F
0010
0011
0012
0013
Error
code
Watchdog timer error in CPU Unit 00
CPU Unit service monitor error
Other CPU error
CPU Unit initialization error
Insufficient System Setup Area
Event timed out
CPU Unit memory error
CPU Unit protected
Error Log Error Codes
Meaning
Each error is recorded as one record in an error log table. Up to 64 records
can be saved. If more than 64 errors occur, the oldest errors will be deleted
from the error log and the most recent error will be recorded.
The following information is recorded in the error log table.
When an error is detected, the error codes and time stamp are recorded in the
error log in RAM inside the Ethernet Unit. Serious errors are also recorded in
EEPROM. The maximum number of errors that can be saved to EEPROM is
64 for the CS Series and 32 for the CJ Series. The errors recorded in
EEPROM will be saved even if the Unit is restarted or power is turned OFF.
When the Ethernet Unit is started, the contents of the error log in EEPROM is
copied to RAM.
When a FINS command is used to read the error log, the log held in RAM is
read. When a FINS command is used to clear the error log, the logs held in
both RAM and EEPROM are cleared.
The following FINS commands can be used to read or clear the error log.
Refer to SECTION 7 FINS Commands Addressed to Ethernet Units.
The error codes are described in the following table. The detailed error code
will provide detailed information on an error.
21
MRC
• Main error code (See table later in this section.)
• Detailed error code (See table later in this section.)
• Time stamp (from the clock in the CPU Unit)
Command
code
00
Monitor time (ms)
Bit 11: Unit not in Registered
I/O Tables
Other bits are reserved for
system use.
00
MRC
01: Read
error
02: Write
error
00
02
03
SRC
1st byte
Detailed error code
ERROR LOG READ
ERROR LOG CLEAR
00
00
00
SRC
03: Routing
table
04: Setup
error
05: CPU Bus
Unit Words
(CIO/DM)
00
2nd byte
Check the operating environment. Saved
Create the I/O tables.
Replace the CPU Unit.
Reduce the number of CPU Bus
Units.
01: Recreate the data specified by
the 2nd byte of the detailed error
code.
02: Clear memory using proce-
dure in the PLC operation manual.
Remove protection from CPU Unit
memory.
Replace the CPU Unit.
Replace the CPU Unit.
Function
Correction
Section 8-3
Saved
Saved
Saved
Saved
Saved
Saved
Saved
PROM
EE-
203