Using FINS Applications
System Configuration Example 2: Using Routing Tables
In this example, an online connection is made via the Ethernet to a PLC on a
Controller Link network (PLC 3 below) from a CX-Programmer/CX-Integrator
connected to the Ethernet network.
Conditions
CX-Programmer's Change PLC Dialog Box
CX-Programmer's Unit Setup
Setup Tab
Same as for System Configuration Example 1.
Routing Table Settings and Transfer to Each PLC
Set the routing tables with CX-Integrator, and transfer them.
1. Using CX-Integrator, connect online, and select Routing table Settings.
PLC name
Network classification
Network Tab
Driver Tab
Settings for target PLC (PLC3)'s Change PLC Dialog Box
• FINS/UDP method
• IP address conversion: Automatic generation method (dynamic)
Routing to final network address 2
requires relaying through node
address 2 of relay network address
1 (Ethernet Unit).
Ethernet (network address 1)
CX-Programmer/CX-Integrator
Then create FINS local routing tables (a local network table and a relay
network table).
Example: PLC 1 Routing Table Settings
Ethernet port
Node address: 1
IP address: 192.168.250.1
FINS destination
Frame length
Response monitor time
Workstation node address
Automatic generation method
IP address
Port number
Routing
according to
routing table
Controller
Link Unit
Controller Link (network address 2)
Ethernet Unit
IP address conversion: Automatic generation method (dynamic)
Controller Link Unit
FINS transmission
source address
Network number
Node address
Gateway between networks
PLC1
Node address 2
Ethernet Unit node address: 2
Ethernet Unit IP address: 192.168.250.2
Ethernet Unit unit number: 0
Controller Link Unit node address: 1
Controller Link Unit unit number: 1
PLC2
Target PLC
PLC3
Ethernet
1
2
3
2,000 bytes
2 seconds
1
Not selected
192.168.250.2
(Ethernet Unit IP
address)
9600
Node address 3
Controller Link Unit
Section 6-5
Setting
PLC3
129