Pulse Inputs
Procedure
Mode 2 Procedure
Procedure
7-5-10 Pulse Input Function Example Application
Example 1:
High-speed Counter
Target Value
Comparison Interrupt
162
1,2,3...
1,2,3...
1,2,3...
1. Set Counter movements (mode 1) in the System Settings (Pulse Input,
2. Turn ON the Measurement Start Bit (A610.02 or A611.02).
3. Monitor the high-speed counter movement value in A604 and A605
1. Determine the Counting Speed, Input Mode, Reset Method, and Counter
2. Wire the input.
3. Make the necessary System Setup settings.
4. Create the necessary ladder programming.
1. Set Frequency measurement (mode 2) in the System Settings (Pulse In-
2. Specify the rotation direction in the Measurement Direction Bit (A610.03).
3. Turn ON the Measurement Start Bit (A610.02).
4. Monitor the high-speed counter’s frequency in A604 and A605.
In this example, pulse input 1 operates a high-speed counter, the high-speed
counter PV is compared in a target-value comparison, and corresponding
interrupt tasks are executed when the target values are reached.
The Reset Bit is kept ON in the program and the PV of the counter is reset
when the phase-Z signal is turned ON after the PV reaches its maximum
value. Before running the program, make the following settings in the System
Setup and restart the FQM1 to enable the new settings.
• Monitor the high-speed counter movement value in A604 and A605
• Counting Speed: 50 kHz or 500 kHz
• Input Mode: Phase Differential, Increment/Decrement, or Pulse + Direc-
• Reset method: Phase Z and software reset, or Software reset
• Counter Operation: Circular Counter or Linear Counter
• Counter Data Display: Frequency measurement (mode 2)
• Turn ON the High-speed Counter 1 Start Bit (A610.00) and start the
• Specify the rotation direction in the Measurement Direction Bit (A610.03).
• Turn ON the Measurement Start Bit (A610.02).
• Monitor the high-speed counter’s frequency in A604 and A605.
(high-speed counter 1) or A606 and A607 (high-speed counter 2).
Counter data display).
(high-speed counter 1) or A606 and A607 (high-speed counter 2).
Operation.
tion
high-speed counter.
OFF is forward, ON is reverse.
put, Counter data display).
Counter 1:
Linear Counter, Counting speed = 50 kHz, Phase Z and software reset,
and Increment/decrement pulse input
Section 7-5