Absolute Positioning with Continually Changing Target Position
Pulse Outputs
Pulse output target
frequency in D00000
and D00001 (BCD)
4,000
Note
0
The pulse output can be stopped by executing ACC(888) with a deceleration
target frequency of 0. However, since the pulse output cannot be stopped at
the correct number of pulses, the deceleration target frequency should not be
set to 0 if it is necessary to output a precise number of pulses.
This example performs absolute positioning (Electronic Cam Control) using a
single-phase pulse output without acceleration/deceleration, and the target
position is updated every cycle. This function relies on a constant cycle time,
in which the ladder program is executed every 2 ms, and positioning is per-
formed using a target value that is changed every cycle according to the
high-speed counter PV.
The pulse output is controlled by the target position, which is calculated
repeatedly from the high-speed counter PV. The target position is calculated,
so the APR instruction can be used for linear approximation.
The high-speed counter is set for circular operation with a circular value of
999 BCD.
(frequency)
reached before speed reaches 0.
Speed
0
200
Specified number of pulses
At this point, the actual number of output
pulses equals the preset number of pulses.
400
600
Time
800
(frequency)
Speed
Speed reaches 0 while the remaining
0
At this point, the actual number of output pulses
may not equal the preset number of pulses.
To be sure that the actual number of output
pulses equals the specified number of pulses,
set the Module so that the speed is greater
than 0 (e.g., the starting frequency) when the
specified number of pulses have been output.
number of pulses is 0 or more.
999
High-speed
Counter PV (BCD)
Section 7-6
Time
191