Troubleshooting Problems in Modules
Output Errors
258
None of the outputs will go ON.
None of the outputs will go OFF.
A specific bit address’ output does not turn ON.
(Indicator is not lit.)
A specific bit address’ output does not turn ON.
(Indicator is lit).
A specific bit address’ output does not turn OFF.
(Indicator is not lit.)
Output of a specific bit number does not turn OFF.
(Indicator lit.)
Output turns ON/OFF irregularly.
Errors occur in 8-point or 16-point blocks, i.e., for the
same common.
Output indicator does not light, but output operates
normally.
Error condition
(1) The load power is not being
(2) Load power supply voltage is
(3) Faulty terminal block connec-
(4) Output circuit is faulty.
Output circuit is faulty.
(1) Output ON time too short
(2) The bit’s status is controlled
(3) Faulty output circuit.
(1) Faulty output device.
(2) Break in output wiring.
(3) Faulty terminal block connec-
Output does not turn OFF due to
leakage current or residual volt-
age.
(1) The bit’s status is controlled
(2) Faulty output circuit.
(1) Low or unstable load voltage. Adjust load voltage to within
(2) The bit’s status is controlled
(3) Malfunction due to noise.
(4) Faulty terminal block connec-
(1) Faulty terminal block connec-
(2) Faulty data bus
(3) Faulty CPU
Faulty indicator or indicator cir-
cuit.
supplied.
too low.
tor contact.
because of a program error.
by multiple output instruc-
tions.
tor.
by multiple output instruc-
tions.
by multiple output instruc-
tions.
tor contact.
tor contact.
Probable cause
Supply power.
Adjust voltage to within the
allowed range.
Replace terminal block connec-
tor.
Replace the Module.
Replace the Module.
Correct program to increase the
time that the output is ON.
Correct program so that each
output bit is controlled by only
one instruction.
Replace the Module.
Replace output device.
Check output wiring.
Replace terminal block connec-
tor.
Replace external load or add
dummy resistor.
Correct program.
Replace the Module.
proper range
Correct program so that each
output bit is controlled by only
one instruction.
Take protective measures
against noise, such as:
(1) Install surge suppressor.
(2) Install isolating transformer.
(3) Install shielded cables
between the outputs and loads.
Replace terminal block connec-
tor.
Replace terminal block connec-
tor.
Replace the Module.
Replace the Module.
Replace the Module.
Remedy
Section 9-3