XW2Z-200J-B10 Omron, XW2Z-200J-B10 Datasheet - Page 84

no-image

XW2Z-200J-B10

Manufacturer Part Number
XW2Z-200J-B10
Description
CONNECTOR CABLE 2M
Manufacturer
Omron
Datasheet

Specifications of XW2Z-200J-B10

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
XW2Z200JB10
Terminal Screws and
Crimp Terminals
Grounding
Wiring
!Caution Tighten AC power supply terminal block screws to a torque of 1.2 N·m. Loose
Note
Note
The terminals on the Power Supply Unit use M4, self-raising terminal screws.
screws may cause shorts, malfunctions, or fire.
(1) Use crimp terminals for wiring.
(2) Do not connect bare stranded wires directly to terminals.
(3) Tighten the terminal block screws to a torque of 1.2 N·m.
(1) Supply power to all of the Power Supply Units from the same source.
(2) Do not remove the protective label from the top of the Power Supply Unit
(3) Do not forget to remove the label from the top of the Power Supply Unit
• GR is the ground terminal. To help prevent electric shock, ground this ter-
PA205R
minal to less than 100 Ω and use special ground wire (minimum cross-
sectional area of 2 mm
Use M4 crimp terminals for AC power supplies.
until the wiring has been completed. This label prevents wire strands and
other foreign matter from entering the Unit during wiring procedures.
after wiring the Unit. The label will block air circulation needed for cooling.
Crimp Terminals for AC Power Supply
7 mm max.
POWER
20 mm max.
AC100-240V
OUTPUT
AC240V
DC24V
INPUT
RUN
L2/N
L1
2
).
Tightening torque 1.2 N
M4 self-raising terminal screws
LG (Noise-filtered neutral terminal)
Ground separately with a resistance of
less than 100 Ω to increase resistance to
noise and to prevent electric shocks.
GR (Ground)
Ground this terminal separately to less
than 100 Ω to prevent electric shock.