XW2Z-200J-B9 Omron, XW2Z-200J-B9 Datasheet - Page 287

no-image

XW2Z-200J-B9

Manufacturer Part Number
XW2Z-200J-B9
Description
CONNECTOR CABLE 2M
Manufacturer
Omron
Datasheet

Specifications of XW2Z-200J-B9

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
XW2Z200JB9
Functions for Servo Drivers Compatible with Absolute Encoders
7-7-9
System Setup
260
Pulse
Input
Tab page
Related Areas
Counter 1
Counter 2
Function
Pulse input
mode
Counter reset
method
Counting Speed
Counter opera-
tion
Counter data dis-
play
Sampling time
(for mode 1)
Pulse input
mode
Counter reset
method
Counting Speed
Counter opera-
tion
Counter data dis-
play
Sampling time
(for mode 1)
0 hex: Phase differential x1
1 hex: Phase differential x2
2 hex: Phase differential x4
3 hex: Increment/decrement pulse input
4 hex: Pulse + direction
0 hex: Software reset
1 hex: Phase Z and software reset
0 hex: 50 kHz
1 hex: 500 kHz
0 hex: Linear counter
1 hex: Circular counter
2 hex: Absolute linear (CW )
3 hex: Absolute circular
4 hex: Absolute linear (CW+)
0 hex: Do not monitor
1 hex: Counter movements (mode 1)
2 hex: Frequency measurement (mode 2)
Note Frequency measurement can be set for
Sets the sampling time when the high-speed counter
PV is being measured (mode 1).
0000 hex: Cycle time
0001 to 270F hex: 1 to 9,999 ms (1-ms units)
Note This setting is used only when the Counter
The counter 2 parameters have the same functions
as the parameters for counter 1, above.
Note The Counter Data Display parameter cannot
counter 1 only.
Data Display parameter is set to 1 hex (mode
1).
be set to frequency measurement (2 hex).
Details
At power ON
Section 7-7
Time when
becomes
effective
setting