7-10-5 Procedure
Analog Outputs
1,2,3...
Note
Note
Outputs can be controlled with SPED(885) and ACC(888) as outlined below.
SPED(885) can be used to change the output value in steps.
F: Analog output value
Specifies the target analog output value as a 4-digit hexadecimal value.
The specified analog output value must be within the allowed range listed
above. If an out-of-range output value is specified, an error will occur and it
will be necessary to switch to PROGRAM mode in order to output the analog
output again.
ACC(888) can be used to generate a rising or falling analog output value
T = Rate of Change (4-digit hexadecimal)
T contains the rate of change (slope) per 2 ms.
T+1 = Analog Output Target Value
T+1 is set to the target analog output value as a 4-digit hexadecimal value.
ACC(888) and SPED(885) can also be used to change the analog output
value while ACC(888) is generating a sloped output.
1. Determine the analog output range, number of outputs, refreshing method,
2. Wire the analog output.
3. Make the necessary System Setup settings (output method).
4. Create the necessary ladder programming.
– 10 to 10 V
0 to 10 V, 0 to 5 V,
1 to 5 V
–10 to 10 V
0 to 10 V, 0 to 5 V or 1 to 5 V
–10 to 10 V
0 to 10 V, 0 to 5 V or 1 to 5 V
(@) SPED
(@) ACC
• Set the analog output range ( 10 to +10 V, 0 to 10 V, 0 to 5 V, or 1 to
• Set the output stop function (clear, peak value, or hold).
• Set the analog output refreshing method (END refresh or immediate
and instructions that will be used.
5 V).
refresh).
#0000
#0000
P
F
T
P
P: Port specifier
M: Always #0000
F: Analog output value
P: Port specifier
M: Always #0000
(#0001 for analog output 1 or #0002 for analog output 2)
(#0001 for analog output 1 or #0002 for analog output 2)
T = Rate of change, T+1 = Analog output target value
EA84 to 157C hex (–5,500 to 5,500 decimal, resolution:
11,000)
FF38 to 1068 hex (–200 to 4,200 decimal, resolution: 4,400)
0000 to 2AF8 hex (0 to 11,000 decimal)
0000 to 1130 hex (0 to 4,400 decimal)
EA84 to 157C hex
(–5,500 to 5,500 decimal, resolution: 11,000)
FF38 to 1068 hex
(–200 to 4,200 decimal, resolution: 4,400)