5-8-2
Operation of FAL(006)
Diagnostic Functions
Failure Alarm Functions
1,2,3...
Note
The number of records is stored in binary in the Error Log Pointer (A408). The
pointer is not incremented when more than 20 errors have occurred.
The FQM1 does not support a clock and the time data in the error log will
always be 0101.
The FAL(006) and FALS(007) instructions generate user-defined errors.
FAL(006) generates a non-fatal error and FALS(007) generates a fatal error
that stops program execution.
When the user-defined error conditions (input conditions for FAL(006) or
FAL(007)) are met, the Failure Alarm instruction will be executed and the fol-
lowing processing will be performed.
1. The FAL Error Flag or FALS Error Flag in the Auxiliary Area is turned ON.
2. The corresponding error code is written to the Auxiliary Area.
3. The error code is stored in the Error Log.
4. The error indicator on the front of the Modules will flash or light.
5. If FAL(006) has been executed, the Modules will continue operating.
When input condition A goes ON, an error with FAL number 2 is generated
and A402.15 (FAL Error Flag) is turned ON. Program execution continues.
Error code
C101
80C0
4102
A
If FALS(007) has been executed, the Modules will stop operating. (Pro-
gram execution will stop.)
1
2
20
Order of
occurrence
A408
A100
A101
A102
A103
A104
A105
A106
A107
A108
A109
A195
A196
A197
A198
A199
Error Log Area
4
0
0
0
C
0
0
0
8
0
0
0
FAL
0 C 0
1 0 2
1 0 1
1 0 1
1 0 1
1 0 1
1 0 1
1 0 1
1 0 1
1 0 1
1 0 1
1 0 1
#0000
Error Log Pointer
002
Error code
Error contents
Error code
Error contents
Error code
Error contents
Section 5-8
121