Motion Control Module Errors
Input Errors
Troubleshooting Problems in Modules
The Motion Control Module’s RUN indicator does
not go ON.
Motion Control Module does not operate or does not
operate properly.
A particular I/O point does not operate.
Error occurs in 8-point or 16-point units.
A particular I/O point stays ON.
None of a particular Module’s I/O points will go ON.
None of inputs turn ON.
(Indicators are not lit.)
None of inputs turn ON.
(Indicators are lit.)
None of inputs turn OFF.
A particular input does not turn ON.
A particular input does not turn OFF.
Input turns ON/OFF irregularly.
Errors occur in 8-point or 16-point blocks, i.e., for the
same common.
Input indicator does not light, but input operates nor-
mally.
Error condition
Error condition
An error in program is causing a
fatal error
The I/O bus is faulty.
(1) External input power supply
(2) The external input power
(3) Terminal block connector is
Input circuit is faulty.
Input circuit is faulty.
(1) Input device is faulty.
(2) Input wiring disconnected.
(3) Faulty terminal block connec-
(4) External input’s ON time is
(5) Faulty input circuit
(6) An input bit address is used
(1) Input circuit is faulty.
(2) An input bit address is used
(1) External input voltage is low
(2) Malfunction due to noise.
(3) Faulty terminal block connec-
(1) Faulty terminal block connec-
(2) Faulty data bus
(3) Faulty CPU
Faulty indicator or indicator cir-
cuit.
is not being supplied.
supply voltage is too low.
not making good contact.
tor contact.
too short.
in an output instruction.
in an output instruction.
or unstable.
tor contact.
tor contact.
Probable cause
Probable cause
Correct program.
Replace the Motion Control
Module.
Connect a proper external input
power supply.
Adjust supply voltage to within
proper range.
Replace terminal block connec-
tor.
Replace the Module.
Replace the Module.
Replace the input device.
Check input wiring.
Replace terminal block connec-
tor.
Adjust input device
Replace the Module.
Correct program.
Replace the Module.
Correct program.
Adjust external input voltage to
within the proper range.
Take protective measures
against noise, such as:
(1) Install surge suppressor.
(2) Install isolating transformer.
(3) Install shielded cables
between the inputs and loads.
Replace terminal block connec-
tor.
Replace terminal block connec-
tor.
Replace the Module.
Replace the Module.
Replace the Module.
Remedy
Remedy