7-6-13 Pulse Output Function Procedures
Pulse Outputs without Acceleration/Deceleration (PULS(886) + SPED(885))
184
1,2,3...
Note
The pulse output direction priority mode for the PLS2(887) instruction is spec-
ified by setting the ON/OFF bit status of A628.14 before executing the
PLS2(887) instruction.
The priority mode setting in A628.14 applies to both pulse output 1 and 2.
Execute PLS2(887) with A628.14 OFF.
Execute PLS2(887) with A628.14 ON.
This procedure shows how to use PULS(886) and SPED(885) to generate a
single-phase pulse output without acceleration or deceleration. The number of
output pulses cannot be changed during positioning.
1. Determine pulse output port.
2. Wire the output.
3. Make the necessary System Setup settings (Pulse Output Tab Page − Op-
D00000
D00001
D00002
D00003
D00004
D00005
D00006
D00007
Execution condition
D00000
D00001
D00002
D00003
D00004
D00005
D00006
D00007
• Select pulse output 1 or 2.
• Output: CW and CCW
• Output power supply: 5 V DC
• Set the pulse output operation mode (in the Pulse Output Tab Page −
eration Mode).
Operation Mode) to relative pulse output, absolute linear pulse output, or
absolute circular pulse output.
CW Output
P_On
8000
0000
C350
0000
0000
0000
03E8
03E8
8000
0000
C350
0000
0000
0000
03E8
03E8
Target position: 8000 Hex
Target speed: 50 kHz
Starting speed: 0 Hz
Acceleration rate: 1,000 Hz
Deceleration rate: 1,000 Hz
Target position: 8000 Hex
Target speed: 50 kHz
Starting speed: 0 Hz
Acceleration rate: 1,000 Hz
Deceleration rate: 1,000 Hz
A628.14
@PLS2
@PLS2
D00000
D00000
#1
#0
#1
#0
Pulse output 1
CW direction
Setting table: D00000
Pulse output 1
CW direction
Setting table: D00000
The direction setting is
ignored and the direction
is changed automatically.
Section 7-6