9-2-12 I/O Check
Error Processing
Check the SOL1 solenoid.
Check the 0001.00 terminal
voltage with a multimeter.
Check voltage at the 0000.02
and 0000.03 terminals with a
multimeter.
Replace the Module.
indicator for CIO 0001.00
for 0000.02 and 0000.03
Is the voltage normal?
Is the voltage normal?
Input indicators
Is the output
normal?
normal?
Start
Yes
Yes
Yes
Yes
No
Yes
No
No
No
No
Disconnect external wiring and
check conduction status, etc.
Disconnect external wiring,
connect a test input, and
check voltage again.
Wire terminals correctly.
Check input devices LS1 and
LS2.
Is the voltage normal?
Is the voltage normal?
Is the output wiring
correct?
No
Yes
Yes
The I/O check flowchart is based on the following ladder diagram section,
assuming that the problem is SOL1 does not turn ON.
No
Yes
Replace the terminal block
connector.
Check voltage at the 0000.02
and 0000.03 terminals with a
multimeter.
Return to Start of I/O Check.
Wire terminals correctly.
Is the voltage normal?
Did the terminal's
Is the input wiring
contact fail?
No
No
correct?
Yes
No
Yes
Replace the Module.
Tighten terminals screws.
CIO 0000.02
CIO 0005.00
(LS1)
CIO 0000.03
(LS1)
Yes
Monitor the ON/OFF status of
CIO 0001.00 from the CX-
Programmer.
Replace the terminal block
connector.
CIO 0001.00
Operation normal?
Did the terminal's
Are the terminal
screws loose?
SOL1
contact fail?
No
Yes
Yes
Replace the Module.
Section 9-2
No
No
255